ACD320 user manual
Parameter Description
- 85-
F4.11
Fault auto-reset times
0
~
3
0
F4.12
Interval time setting of
automatic resetting fault
0.1
~
100.0s
1.0s
Fault auto-reset times: used to set the auto-reset times when inverter chooses fault auto-reset.
If this value is exceeded, inverterwill wait for trouble shooting.
Interval time setting of fault auto-reset: chose the interval time between fault occurring and
automatic resetting actuated.
Function Code
Name
Setting Range
Default
Value
F4.13
FDT level detection value
0.00
~
F0.04
50.00Hz
F4.14
FDT delay detection value
0.0
~
100.0%(FDTlevel)
5.0%
Set output frequency detection value and the delay value of output action dismissed, as
shown by following figure:
Fig.6-16 FDT LevelDiagram
Function Code
Name
Setting Range
Default
Value
F4.15
Frequency reaching
detection range
0.0
~
100.0%(maximum
frequency)
0.0%
When the inverter output frequency reaches the set frequency value, this function can
regulate its detect ion range value, as shown by following figure: