ACD320 user manual
Parameter Description
- 95-
Fig. 6-23 Limit current protection
6.7 F6 Communication Parameters
Function Code
Name
Setting Range
Default
Value
F6.00
Communication Address
1~ 247,0 is the broadcast
address
1
When master machine plan to transmit a frame, slave communication address is set to be 0,
it is also broadcast address.All slavemachine inMODBUS will receive this frame but not
response.
Note: slave address is not allowed to set 0.
Local communication address is unique for every slave machinewithin communication
network. This is basis of utilization of point to point communication betweenmaster machine and
inverter.
Function Code
Name
Setting Range
Default
Value
F6.01
Baud rate setting
0:1200BPS
1:2400BPS
2:4800BPS
3:9600BPS
4:19200BPS
5:38400BPS
3
This parameter is used to set transmission rate.
Function Code
Name
Setting Range
Default
Value