ACD320 user manual
Parameter Description
- 70-
F2.01
MI1 Terminal Function
Selection
0
~
31
0
F2.02
MI2 Terminal Function
Selection
0
~
31
0
F2.03
MI3 Terminal Function
Selection
0
~
31
0
F2.04
MI4/FWD Terminal
Function Selection
0
~
31
1
F2.05
MI5/REV Terminal
Function Selection
0
~
31
2
F2.06
MI6 Terminal Function
Selection
0
~
31
0
These parameters are used to set up the corresponding functions of digitalmultifunction
input terminals.
Setting
value
Function
Description
0
No Function
Even if there is a signal input, the inverter does not run.
Terminals which are not used can be set to be no function in order
to prevent malfunction
1
Forward
The inverter ’s forward or reverse running can be control by
external terminals.
2
Reverse
3
Three-wire operation
control
By means of this terminal the inverter s operation mode can be
defined to be three-wire control mode. For details, please refer to
the function code description of F2.07 three-wire control mode.
4
Forward Jogging
At Jogging operation, the frequency and Jogging
Acceleration/Deceleration time can be found in detail descriptions
of F4.02,F4.03 and F4.04 function codes.
5
Reverse Jogging
6
Free-run stop
The inverter turns off output, and the motor stop process is not
controlled by the inverter. It is often applied when the inertia
loading is big and there is no requirement on stop time. This mode
has the same definition as F0.19 does.
7
Failure reset
This is external failure reset. It has the same function as STOP
button
on
the
keyboard.
Using
this
function
can
performlong-distance failure reset.
8
External fault input
When external fault signal is input, the inverter reports it and stops.
9
Frequency
up setting
(
UP
)
When the frequency is set by external terminal, modify the
frequency up and down command.When the frequency
source is set as digital setting, the set frequency can be
regulated up and down.
Using terminal can clear UP/DOWNset frequency so that set
frequency can be restored the frequency setting given by frequency
10
Frequency
down setting
(
DOWN
)
11
Frequency up/down
setting clear