17
Kamstrup A/S • 55121739_B1_GB_02.2020
MULTICAL® 403
9.3 Pulse outputs
Pulse outputs for energy and volume are made
with Optp Fet and are available on a number of
the communication modules.
Max voltage and current of the outputs are
45 VDC and 50 mA, respectively.
16 +
Pulse output C
17 -
18 +
Pulse output D
19 -
When a module with pulse outputs is mounted in MULTICAL®, the meter is automatically
configured for pulse outputs. The pulse duration is ordered at 32 ms. or 100 ms. After delivery the
pulse duration can be changed by means of the PC program METERTOOL HCW.
The resolutions of the pulse outputs always follow the least significant digit displayed for energy
and volume respectively.
9.4 Data Pulse, inputs (In-A, In-B),
type HC-003-10
The data terminals are, for example, used for
connecting a PC. The signal is passive and
galvanically separated. In order to read data,
an active converter cable, 66-99-106 (D-SUB
9F) or 66-99-098 (USB type A) is required. The
converter cable must be connected as follows:
62
Brown
(DAT)
63
White
(REQ)
64
Green
(GND)
9.5 Data Pulse, outputs (Out-C, Out-D) ,
type HC-003-11
The data terminals are, for example, used for
connecting a PC. The signal is passive and
galvanically separated. In order to read data,
an active converter cable, 66-99-106 (D-SUB
9F) or 66-99-098 (USB type A) is required. The
converter cable must be connected as follows:
62
Brown
(DAT)
63
White
(REQ)
64
Green
(GND)