4
Kamstrup A/S • 55121739_B1_GB_02.2020
MULTICAL® 403
1 General information
'
Please read this guide carefully before mounting the energy meter.
In case of incorrect mounting, Kamstrup's guarantee obligations no longer apply.
Please note that the following installation conditions must be obeyed:
- Pressure stage:
PN16/PN25, see marking.
- Pressure stage, Kamstrup
sensor pair type DS:
PN25
- Pressure stage, Kamstrup
pocket sensors type PL:
PN25
At medium temperatures above 90 °C we recommend flange sensors as well as wall-mounting of
calculator.
At medium temperatures below ambient temperature, MULTICAL® 403 must be wall mounted and
the condensation-proof version, type 403-C, must be used.
In case of bidirectional heat/cooling
energy metering, type 403-T is used.