Katherm QK -
Trench convector with energy-efficient EC tangential fan
1.42
Ready-to-install convector-based trench convectors
Assembly and installation instructions
Installation of the control unit
Installation/dismantling
Electrical wiring
Connect the KaController to the nearest
Ka
therm
QK according to the
wiring diagram. The maximum BUS length between the KaController and
the unit is 30 m.
• The respective
Ka
therm
QK automatically becomes the master unit in the
control circuit when a KaController is connected to it.
DANGER!
Disconnect the unit prior to embarking on any wiring work!
Only connect the bus lines when the unit is fully disconnected.
DIP switch setting
• The DIP switches on the rear of the KaController should be set according
to the illustration at the side:
DIP switch no. 1:
ON
DIP switch no. 2:
OFF
PCB fault messages
Any fault messages are shown in the KaControl remote controller
display.
KaController terminals
DIP switch setting
KaController
DIP switch no. 1:
ON
DIP switch no. 2:
OFF
Code
Alarm
A11
Faulty control sensor
A13
Room frost protection
A14
Condensation alarm
A15
General alarm
A16
Faulty AI1, AI2 or AI3 sensor
A17
Unit frost protection
A18
Faulty EEPROM
A19
Offline slave in the CANbus network
tAL1
Temperature sensor in KaController faulty
tAL3
Real-time clock in KaController faulty
tAL4
EEPROM in KaController defective
Cn
Communication fault with the external control board (PCB)