Cleaning the tangential fan
A dirty tangential fan impairs the airflow and thus also the output of the
unit.
• If dirty, carefully clean the surfaces of the tangential fan with a cloth.
Clean the floor trench
A dirt floor trench, possibly caused by coarse dirt, impairs the airflow.
• If dirty, carefully vacuum the floor trench or use a cloth to clean if after
removing all components (grille, lid, bracing, tangential fans).
Clean the convector
A dirt convector, e.g. dusty deposits between the fins, impairs the airflow,
heat transfer and thus also the output of the unit.
• Carefully vacuum the heat exchanger if dirty. Do not use water to clean
the heat exchanger!
Caution:
Fins bend easily!
10.1 Maintenance schedule
Interval
Maintenance task
as required
Visual inspection of the grilles (roll-up or linear), if dirty, remove and use a cloth to clean
every six months
Visual inspection of the tangential fans; remove and clean if dirty
(see “Cleaning tangential fans”)
every six months
Visual inspection of the floor trench; remove internal components and clean if dirty
(see “Cleaning the floor trench”).
every six months
Visual inspection of the convector; clean if dirty
(see “Cleaning the convector”)
every six months
Check the water-side connections and valves for leaks.
every six months
Check that the electrical cables and connections are tight.