17
Katherm QK -
Trench convector with energy-efficient EC tangential fan
1.42
Ready-to-install convector-based trench convectors
Assembly and installation instructions
11.1 Overview of controls
The
Ka
therm
QK comes in a series of different electrical versions.
Connect it via a terminal strip in the electrical junction box. This is located
on the side of the
Ka
therm
QK’s water connection.
Wire the unit as per the wiring diagram, which is different for each version.
Ask a qualified electrician to determine the type of cable and cable cross-
sections: The cable cross sections basically depend on the fuses for the cable
length and the wiring capacity of the electric motors on site .
Lay control lines separately from supply lines.
Use UNITRONIC® BUS LD 2x2x0.22 or similar as data cables.
Wire the unit in series: star cabling is not allowed.
11.2 Electrical wiring
Suggested layout for control option KaControl C1
The connection for the electrical cables is in the control box. To connect the
electrical cables, open the control box, insert the cables and connect them
up according to the wiring diagram (supplied with the unit).
Design
Art. no. suffix
24 V electromechanical
_24
230 V electromechanical
_00
KaControl
_C1
Fig. Katherm QK with control box and
mains feed