13
KaCool D AF –
Comfortable feeling of well-being, thanks to AtmosFeel
3.25
Chilled water air conditioning system
Installation and operating instructions
3.2 Connection values
Unit size
Model 1
Model 2
Model 3
Model 4
Model 5
Model 6
Model 7
Mains voltage
230 V / 50 Hz
Enclosure type
IP 21
Protection class
I / Protective conductor connection
AC fan model
Max. power consumption
W
43
63
75
89
102
108
156
Max. power consumption
A
0.19
0.28
0.33
0.39
0.52
0.6
0.75
EC fan model
Max. power consumption
W
11
26
45
65
81
89
155
Max. power consumption
A
0.11
0.22
0.33
0.47
0.52
0.55
0.72
1)
at CHW 7 / 12, tL1 = 27 °C
2)
at LPHW 70/60, tL1 = 20 °C
3.3 Operating data
Valve
configuration
2-pipe system
4-pipe system
Model
Dimensions
(L x W)
Cooling outputs
1)
Heat outputs
2)
Cooling outputs
1)
Heat outputs
2)
[kW]
[kW]
[kW]
[kW]
[mm]
AC, 230 V
1.97 – 2.71
3.85 – 5.27
1.89 – 2.75
2.45 – 3.50
1
680 x 680
2.17 – 4.31
4.19 – 8.19
1.91 – 3.40
2.45 – 4.45
2
2.73 – 5.05
5.17 – 9.86
2.00 – 3.89
1.91 – 3.30
3
4.03 – 5.47
8.21 – 10.88
2.66 – 4.47
2.39 – 3.70
4
4.19 – 6.22
8.46 – 12.85
4.50 – 6.20
5.80 – 9.00
5
930 x 930
5.38 – 9.56
9.22 – 17.30
4.30 – 7.20
6.30 – 10.50
6
5.38 – 11.00
10.09 – 22.66
4.50 – 8.80
6.80 – 12.50
7
EC, 230 V
1.97 – 2.71
3.85 – 5.27
1.89 – 2.75
2.45 – 3.50
1
680 x 680
2.17 – 4.31
4.19 – 8.19
1.91 – 3.40
2.45 – 4.45
2
2.73 – 5.05
5.17 – 9.86
2.00 – 3.89
1.91 – 3.30
3
4.03 – 5.47
8.21 – 10.88
2.66 – 4.47
2.39 – 3.70
4
4.19 – 6.22
8.46 – 12.85
4.50 – 6.20
5.80 – 9.00
5
930 x 930
5.38 – 9.56
9.22 – 17.30
4.30 – 7.20
6.30 – 10.50
6
5.38 – 11.00
10.09 – 22.66
4.50 – 8.80
6.80 – 12.50
7
Summary of Contents for KaCool D AF
Page 103: ......