15
KaCool D AF –
Comfortable feeling of well-being, thanks to AtmosFeel
3.25
Chilled water air conditioning system
Installation and operating instructions
1
Compact basic housing:
galvanised steel
the outside has a fleece coating
for improved insulation from the
environment
the inside has high-grade
10 mm vapour diffusion-tight
polyethylene foam matting
2
Punched holes for external air
outlet:
connection option for on-site air
outlets
3
Punched hole for optional fresh
air connection:
model 1-4, per spigot (max. 2)
80 m³/h
model 5 - 7, (max. 1) 120 m³/h
4
AtmosFeel air outlet:
four manually adjustable outlet
air slats (model 1 - 4)
smooth plastic
easy to clean
5
Electrical junction box for
control PCBs:
KaControl
infra-red electronic receiver
terminals only, for on-site control
6
Design panel, similar to RAL
9010 (pure white)
outlet optimised for maximum
comfort through side air outlets
and utilisation of the Coanda
effect
IR receiver concealed within the
design panel (models 1 – 4)
7
Condensation connection:
outside diameter 13.5 mm
8
Air filter G1:
simple to remove
easy to clean
9
Air intake grille
large free cross-section to
minimise pressure losses
10
Hydraulic connections:
for CHW, LPHW and
condensation drain
valve drip tray drains any
condensation produced into the
condensation tray
drip tray is supplied with the unit
optionally available with built-
in valves with corresponding
quantities
11
Condensation pump and float
switch:
easily accessible by removal of
the polystyrene condensation
tray
integrated condensation pump
drains the condensation up to a
max. head of 480 mm
pump activation by a two-stage
float switch
the pump is switched on when
the first stage is reached, and
the second stage activates an
evaluable alarm contact
12
Fans
3-stage AC fans
continuously variable EC fans
efficient and low-noise
protection class IP 44, insulation
class B
integrated thermal contacts
to prevent the motor from
overheating
13
Heat exchanger
copper pipe with aluminium fins
2-/ 4-pipe version
vent and drain valves on the
outside of the unit
14
Valves (optional):
optionally factory-integrated
7
Condensation connection
9
Intake air grille
8
Air filter G1
Example; Models 1 – 4
Summary of Contents for KaCool D AF