KaCool D AF –
Comfortable feeling of well-being, thanks to AtmosFeel
Chilled water air conditioning system
Installation and operating instructions
6.6 Electro-mechanical model with EC fan
The required room temperature and fan stage and, if
necessary, heating or cooling mode are set on the climate
controller. The fan runs from a certain difference between
the set room temperature and the actual value and the
thermoelectric actuator opens the water-side valve.
If a condensation alarm is fitted, the PCB fitted in the cassette
for the condensation pump closes the cooling valve and opens
the max. 24 V AC/2 A potential-free alarm contact.
The climate controller type 30155 and type 30256 enables the
operation and temperature control of a max. of 2 parallel
wired KaCool D AF (230 V electromechanical version with EC
fan).
Set the room temperature on the climate controller type 30155
using the dial and fan stage in manual mode via a 3-stage slider
switch or continuously variably in automatic mode.
The room temperature is set on the climate controller with
clock type 30256 using sensor-controlled function keys.
With manual 10-stage fan speed adjustment, automatic
summer/winter changeover and a day or week program.
A separate room temperature sensor type 148921, a potential-
free contact can be connected to both climate controllers for
switchover to ECO mode or On/Off and, with 2-pipe systems,
a clip-on sensor type 148922 can be connected in conjunction
with a 3-way valve or a potential-free contact for heating/
cooling switchover, although there are only 2 inputs available
on the climate controller type 30256 which can be used
depending on the configuration.
EC climate controller type 30155
EC climate controller with clock
type 30256
Electrical junction box
Terminals for the condensation
alarm contact