1.96
Climate Controller Type 148941 / Type 148942 / Type 148943 / Type 148944
Operation manual
30
11 Parameter List
Menu
Parameter
Default
setting
Min
Max
Unit
Comment
Setpoints
Base setpoint
22
0
50
°C
Adjustment range
3
0
10
K
Increment
1
0,1
2
K
Minimum
8
0
20
°C
Maximum
32
20
50
°C
Frost protection
8
-10
10
°C
Heat protection
40
25
60
°C
Unit frost protection
4
-10
10
°C
Presence/Offset
Reset
-
-
-
Hold: Offset is retained when changing from occupied to unoccupied.
Reset: Offset is set to 0 when changing from occupied to unoccupied.
Fan levels/General
Number of stages
5
0
5
-
Minimum
0
0
100
%
Minimum fan speed
Maximum
100
0
100
%
Maximum fan speed
Start-up time
1
0
10
S
Time for fan actuation with max. control voltage at start-up
Assignment
H/C
-
H/C:
Fan is actuated in heating and in cooling mode.
H:
Fan is actuated only in heating mode.
C:
Fan is actuated only in cooling mode.
Switching behaviour
-1
-1
100
%
Fan speed restriction
M/A
-
M/A: The speed limit is enabled in automatic and manual mode
A:
The speed limit is only enabled in automatic mode
Fan levels/Threshold levels
Hysteresis
1,0
0
3
C
Release
Off
-
Off:
Threshold values are not taken into account for activation of fan
stages in cooling mode.
On:
Release of fan stages on the basis of the threshold values and
changeover sensor.
Fan levels/Threshold levels/Heating
Stage 1 (20%)
29
0
100
°C
Stage 2 (60%)
31
0
100
°C
Stage 3 (100%)
33
0
100
°C
Fan levels/Threshold levels/Cooling
Stage 1 (20%)
18
0
100
°C
Stage 2 (60%)
18
0
100
°C
Stage 3 (100%)
18
0
100
°C
Inputs/Potential-free/Input 1/Functions
External sensor
Disabled
-
Intake air sensor
Disabled
-
Changeover DI
Disabled
-
Changeover sensor
Disabled
-
Window contact
Disabled
-
Condensation alarm
Disabled
-
Dewpoint contact
Disabled
-
Presence contact
Disabled
-
Key card switch
Disabled
-
On / Off
Disabled
-