1.96
Climate Controller Type 148941 / Type 148942 / Type 148943 / Type 148944
Operation manual
25
9.3 Electrical Wiring
Term.
connection Type
1
EC fan
GND
2
EC fan
0…10 V, max. 5 mA
3
4
Output 2
230 V AC, max. 3A
5
Output 1
230 V AC, max. 3A
6
Input 3
Digital/230 V AC
7
L
8
N
9
Input 1
Universal/potential-free
10
11
Input 2
Digital/potential-free (type: 148941 & 148942)
Modbus interface (type: 148943 & 148944)
12
9.4 Cabling
•
Route all low voltage cables along
the shortest route.
•
Ensure that low voltage and power
cables are separated, using metal
partitions on cable harnesses.
•
Use only shielded cables as low
voltage cables
Important
•
*): Shielded cable, IY(ST)Y 0.8 mm or similar. Lay separately
from high-voltage cables.
•
**): Shielded paired cable e.g UNITRONIC® BUS LD 2x2x0.22
or similar. Lay separately from high-voltage cables.
•
All other connections can be done with NYM-J (or similar).
•
Wire cross-sections of unshielded cables are not specified, as
the length of the cable is involved in the calculation of the cross-
section.
•
Specifies the number of wires including protective conductor.