1.96
Climate Controller Type 148941 / Type 148942 / Type 148943 / Type 148944
Operation manual
29
10 Modbus Settings
10.1 Modbus Interface Configuration
To configure the Modbus interface, please open Modbus
settings by pressing 5 and 6 simultaneously for
approximately 3 seconds.
The modbus master interface and the climate control
interface (as a slave) have to be adjusted equally.
The default settings of the modbus interface are:
Transmission Code:
RTU, Slave Mode
Adresse:
32
Baud Rate:
19200
Parity:
Gerade
Stop Bits:
2
10.2 Modbus - Parameter List
Datenpunktbeschreibung
Wertebereich
Registertyp
Protokoll Adresse
Intern temperature sensor
0
– 500
≙
0
– 50°C
Input Register
514
Extern temperature sensor
0
– 500
≙
0
– 50°C
Input Register
515
Operating condition controller
0: Off
1: Heating
2: Cooling
Input Register
525
Control variable controller
0
– 100
≙
0
– 100%
Input Register
524
Alert notification
11: Control sensor damaged
12: Engine error
13: Room frost protection
14: Condensation alarm
15: General error
16: Extern sensor damaged
17: Unit frost protection
Input Register
528
Filter alert
0: inactive
1: active
Input Register
529
State input 1
0: open
1: closed
Input Register
519
State input 3
Input Register
520
Heating Setpoint
0
– 500
≙
0
– 50°C
Input Register
511
Cooling Setpoint
0
– 500
≙
0
– 50°C
Input Register
512
Offset Setpoint
0
– 500
≙
0
– 50°C
Input Register
513
Default setpoint Offset
-90
– 90
≙
-9,0
– 9,0°C
Holding Register
257
Default operating condition On/Off
0: On
1: Off
Holding Register
262
Eco / Day
0: Eco
1: Day
Holding Register
264
Default Change - Over
0: Heating
1: Cooling
65535: no Function
Holding Register
261