1.96
Climate Controller Type 148941 / Type 148942 / Type 148943 / Type 148944
Operation manual
33
Menu
Parameter
Default
setting
Min
Max
Unit
Comment
Sensor settings
Internet offset
0
-9.9
9.9
K
External offset
0
-9.9
9.9
K
Unit
°C
-
°C
°F
Controller/General
Hysteresis
0.3
0
15
K
Start mode
Auto
Neutr. zone 4-p
0.4
0
15
K
Standby
5
0
15
K
Eco setback
3K
0
15
Eco boost
3K
0
15
Presence/Eco
Over
Controller/Heating
Type
PI
-
PI
2 point
Xp
1.5
0
25
K
Tn
Off
0
100
min
Natural convection
0,5
0
25
K
Regulator/Cooling
Type
PI
-
PI
2 point
Xp
2.0
0
25
K
Tn
Off
0
100
min
Natural convection
0.0
0
25
-
Unit settings/Status after Power On
Standby
Disabled
-
Last status
Disabled
-
On
Active
-
Unit settings/Values after Power On
Retain
Disabled
-
Reset
Active
-
Unit settings/Language
German
Active
-
English
Disabled
-
Unit settings/Lighting
Brightness of LCD
90
0
100
%
Brightness of LED
20
0
100
%
Unit settings/Filter
Filter alarm
0
0
104
Unit settings/Factory setting
Factory setting
Disabled
Keys
AUTO fan
Yes
-
Yes:
Automatic mode can be set
No:
Automatic mode cannot be set
Keys/Central key
No special function
Active
-
Presence toggle
Disabled
-
Room occupied
Disabled
-
Room unoccupied
Disabled
-
Locked
Disabled
-