- Condensate drain connection
Connection of the condensate drain depends on the
type of machine installation (ceiling or wall).
Connect the condensate drain to the domestic sewage
system using a duct or pipe (siphoned).
To prevent suction or emptying of this drain,
the height of the siphon must not be less than 100mm.
The machine is supplied with a section of flexible
corrugated condensate drain pipe, 800 mm long,
pre-assembled with a 90°C bend coupling (see Fig.2).
The component facilitates the connection in the event
of horizontal installation and allows the siphon to be
fitted with iron wire support.
Connections must only be carried out by qualified
personnel to avoid damage or injury
(Fig. 2)
Attention: the impropre installation of the
unit and the incorrect connection of the
condensate drain pipe can hinder the re-
quired condensate drainage with its consequent
leackage.