![background image](http://html1.mh-extra.com/html/kaeser-kompressoren/hbpi-pr/hbpi-pr_installation-and-operating-manual_3172311047.webp)
Fig. 23 Recommended machine placement and minimum dimensions [in.]
A
32.0
B
39.4
C
59.1
D
59.1
E
39.4
1
Exhaust fan
2
Air inlet aperture
➤ If the ambient temperature is too low: Heat the machine room adequately or install an auxiliary
heater.
➤ Ensure accessibility so that all work on the machine can be carried out without danger or hin‐
drance.
➤ Do not position the machine in the warm exhaust air flow from other machines.
➤ When installing multiple machines, ensure that all intake and exhaust air openings are ar‐
ranged at one side.
➤ If installed outdoors, protect the machine against frost, direct sunlight, dust, and rain.
5.2.2 Ensuring adequate ventilation
If the ventilation is insufficient, a partial vacuum can be created in the room.
➤ Ensure that the volume of air flowing into the machine room is at least equivalent to that being
removed from it by the machine and exhaust fan.
➤ Make sure that a sufficient amount of oxygen is supplied to individuals in the machine room.
➤ Make sure that the machine and exhaust fan can only operate when the inlet aperture is ac‐
tually open.
➤ Keep the inlet and exhaust apertures free of obstructions so that the cooling air can flow freely
through the room.
➤ Ensure clean air in order to support the proper functioning of the machine.
5
Installation and Operating Conditions
5.2
Installation conditions
Number: 9_9572 28 USE
Installation and Operating Manual Rotary lobe blower
HBPI pr
37