Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
Increasing output gra-
dient & Decreasing
output gradient
1 - 65534 [% / min]
NOTE: In addition to configuring the transient behavior using the set-
tling time corresponding to a first-order filter, the reactive power set-
ting can be determined by a maximum gradient - maximum change in
the reactive power per time period.
1 Maximum change in the reactive power %Smax/min in the event of
a change to over-excited mode.
2 Maximum change in the reactive power %Smax/min in the event of
a change to under-excited mode.
4
1
2
3
4
Settling time
1 – 120 [s]
F
Set the response speed of the Q(U) control.
4
1
2
3
4
Minimum cos-phi Q1
- Minimum cos-phi Q4
0 – 1
NOTE: In the event of a significant voltage deviation, the maximum re-
active power adjustment range can be limited by a minimum cos φ in
order to prevent an excessive reactive power supply and, as a result, a
significant reduction in the maximum active power that can be fed in.
F
Enter the minimum cos ϕ factor for quadrants 1 and 4.
4
1
2
3
4
Q(U) active curve
1 - 4
F
Select the active curve.
NOTE: Up to 4 characteristic curves can be configured independently
and one of them can be activated for regulation each time.
4
1
2
3
4
Priority mode
Q-Priority | P-Prior-
ity
F
Set priority for reactive power - Q or active power - P.
NOTE: When it comes to P priority, the reactive power adjustment
range is limited subject to the active power that is currently available
and fed in.
4
1
2
3
4
Number of nodes
2 - 10
NOTE: The maximum number of configurable nodes depends on the
selected grid type.
F
Specify the number of nodes.
4
1
2
3
4
Node 1- Node 10
Power / Excitation /
Voltage
0 – 100 [%]
F
Set the reactive power of the node as a percentage of the maximum
power.
Over-excited | un-
der-excited
F
Select the type of phase shift.
NOTE: Over-excited relates to a capacitive load, under-excited relates
to an inductive load.
0 – 100 [% Unom]
F
Enter the voltage of the node in volts.
NOTE: The voltage values of the nodes must increase continuously. For
voltages below the 1st node and voltages above the last node, the re-
active power value of the 1st or last node is used each time.
4
1
2
3
4
Frequency dependent
power reduction
NOTE: Activate frequency-dependent power reduction in the P(f)
menu.
Not for IL,
IT
4
1
2
3
4
P(f) operation mode
Off | Mode 1 |
Mode 2
F
Specify the operation mode.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3