8
Start-up
8.1
Conditions
DANGER
Lethal voltages are still present in the connections and cables of the device even after the device has
been switched off and disconnected!
Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched.
›
The device is only permitted to be put into operation by a specialist.
›
Unauthorized persons must not be able to access the device.
WARNING
Risk of burning due to hot surface
Heat sinks become very hot during operation.
›
Never touch the heat sinks after starting up the device.
›
Wait until a cooling time of at least 10 minutes has elapsed before starting the cleaning process.
↻
The device has been mounted and electrically installed.
↻
The PV generator supplies a voltage above the configured start voltage.
NOTE: Warning: Test for function of likziel
1 Connect the grid voltage using the external circuit breakers.
2 Connect the PV generator using the DC isolator switch (0 > 1)
»
The device begins operation.
»
During initial start-up: Follow the instructions of the New Connection Wizard.
NOTE
A mobile terminal device with WIFI interface is required in order to put the device into operation.
The following functions are only available via the WEB interface:
›
Initial start-up
›
Parameterization
›
Resetting the device to its factory defaults
NOTE
We recommend using an up-to-date Firefox or Chrome browser or the default browser that is available on
the mobile terminal devices to configure the device via the web interface.
8.2
Preconditions relating to standards
Attachment of safety label in accordance with UTE C15-712-1
The code of practice UTE C15-712-1 requires that, upon connection to the French
low-voltage distribution network, a safety sticker showing a warning to isolate both
power sources when working on the device must be attached to each device.
F
Attach the provided safety sticker to the outside of the device housing where it is
clearly visible.
ATTENTION
Présence de deux
sources de tension
- Réseau de distribution
-Panneux photovoltaïques
Isoler les deux sources
avant toute intervention
Fig. 38:
Adhesive label
UTE_C15-712-1
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Page 33