No. Grid
LED
LED
Display on web interface
Status description
Action
Pers
.
101
Temperature plausibility er-
ror
The individual temperatures in the device are
compared with one another. This fault occurs
if a certain limit value is exceeded.
Notify KACO Ser-
vice!
K
102
Plausibility fault efficiency
The degree of efficiency of the device must re-
main within certain limits.
Notify KACO Ser-
vice!
K
105
Relay plausibility error
Check the voltage measurement upstream of
and between the relays - the difference can be
a maximum of 24 V
Switch off the de-
vice entirely (switch
off AC + DC for min.
5 minutes), if the
fault occurs again,
there is a device
fault
K
107
Check surge protection de-
vice
Surge protection device (if present in the de-
vice) has tripped and must be replaced. AC, DC
& interfaces are monitored for triggered surge
protection. All 3 LEDs light up on the device.
Check surge protec-
tion in the device.
The surge protec-
tion module has a
corresponding func-
tion display. With a
red function display,
the surge protection
module must be
checked, and re-
placed if necessary.
The device feeds
back into the grid.
K
108
Grid failure overvoltage L1
Shutdown because the grid voltage on phase
Lx is outside the set limit value (2nd level up to
5th level of grid monitoring). The limit value is
specified by the respective country-specific
standard.
Check grid voltage
at the device termi-
nal Lx. Check setting
values in the param-
eters menu. Has ev-
erything been set
up correctly and is
the voltage within
the set limit values?
Check connection/
cabling!
E
109
Grid failure overvoltage L2
See description in the event of a fault 108
See action in the
event of a fault 108
-
110
Grid failure overvoltage L3
See description in the event of a fault 108
See action in the
event of a fault 108
-
111
Grid failure undervoltage L1 See description in the event of a fault 108
See action in the
event of a fault 108
-
112
Grid failure undervoltage L2 See description in the event of a fault 108
See action in the
event of a fault 108
-
113
Grid failure undervoltage L3 See description in the event of a fault 108
See action in the
event of a fault 108
-
118
DC overvoltage 1
PV voltage above permissible limit values.
Re-wire PV mod-
ules. Contact your
authorised electri-
cian.
E