Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
Power rampup active
NOTE: Power ramp-up is used to ramp up the power gradually
Power rampup gradi-
ent
1 – 600 [% / min]
F
Set increase.
Rampup on every con-
nect
Status
Rampup on first con-
nect
Status
Rampup after grid fail-
ure
Status
Password Protection
Status
1 Activate option.
2 Activate optional password protection.
3 Confirm action field
4
1
2
3
4
Delta P
NOTE: Option to regulate active power
Operating mode
Status
F
Select operating mode.
active power
-100.00 - +100.00
[%]
Password protection
Status
1 Set the active power.
2 Activate optional password protection.
3 Confirm the action field.
4
1
2
3
4
Features / Functions
NOTE: Input screens for advanced device functions
4
1
2
3
4
External grid protection
disconnection
NOTE: Option to detect the external grid protection devices
External grid protection
Status
F
Select the device.
4
1
2
3
4
Powador-protect
NOTE: Configures the grid shutdown via a Powador-protect connected
to the digital input of the device.
Powador-protect oper-
ation mode
Auto | On | Off
↻
Auto/On: A Powador-protect is operating in the photovoltaic plant
and is connected to the device at the digital input/output.
F
Set the operating mode for Powador-protect.
Auto
: The device automatically detects a Powador-protect integrated
into the photovoltaic plant.
On
: The digital signal of the Powador-protect must be present at the
digital input of the device for the device to start with feed-in.
Off
: The device does not check whether a Powador-protect is integrated
into the PV plant.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3