Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
Connection Conditions
NOTE: Precise switch-on conditions should be specified relative to the
grid conditions.
Min. conn. voltage af-
ter grid mon.
10 – 110 [% Unom] /
&
Max. conn. voltage af-
ter grid mon.
90 – 126.6 [% Unom]
F
Specify switch-on voltage range after grid error.
Min. conn. frequency
after grid mon.
45 – 65 [Hz] / &
Max. conn. frequency
after grid mon.
45 – 65 [Hz]
F
Specify switch-on frequency range after grid error.
Min. conn. voltage af-
ter grid failure
10 – 110 [% Unom] /
&
Max conn. voltage af-
ter grid failure
90 – 126.6 [% Unom]
F
Specify switch-on voltage range after grid error
Min. conn. frequency
after grid failure
45 – 65 [Hz] / &
Max. conn. frequency
after grid failure
45 – 65 [Hz]
F
Specify switch-on frequency range after grid error.
Monitoring grid voltage
1 - 1800 [s]
&
Monitoring PV voltage
1 - 1800000 [ms]
F
Specify the time for monitoring the grid voltage and PV voltage.
Waiting time after grid
failure
1 - 1800 [s]
Password protection
Status
1 Set waiting time after grid error.
2 Activate optional password protection.
3 Confirm the action field.
4
1
2
3
4
Trip Settings
NOTE: Activate shutdown according to generic parameters, frequency
or voltage.
4
1
2
3
4
Generic parameters
NOTE: Opportunity to activate standard protective shutdown
Protection shutdown
with intentional delay
Status
1 If necessary, activate delayed trip-off.
2 Activate optional password protection.
3 Confirm the action field.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3