No. Grid
LED
LED
Display on web interface
Status description
Action
Pers
.
203
Protection shutdown grid
voltage (effective value) L1
Protective shutdown due to an excessively
high grid voltage on Lx. It is the effective value
which is decisive for the shutdown procedure.
Check the AC-side
wiring (e.g. in-
creased voltage due
to inductance ca-
pacity of a trans-
former) If the error
display occurs fre-
quently, or every
time, the installa-
tion must be
checked. If there is
nothing wrong with
the installation,
then there is a fault
in the device.
Check connection/
cabling!
E
204
Protection shutdown grid
voltage (effective value) L2
See description in the event of a fault 203
See action in the
event of a fault 203
-
205
Protection shutdown grid
voltage (effective value) L3
See description in the event of a fault 203
See action in the
event of a fault 203
-
206
Protection shutdown over-
current HW
Overcurrent shutdown triggered by hardware. -
-
207
Detection of hardware de-
tection failed: Control card
The data saved on the control card is erro-
neous.
Disconnect AC and
DC, wait 1 minute
and switch on again.
B
208
Detection of hardware de-
tection failed: AC power
board
The data saved on the AC power board is erro-
neous.
Disconnect AC and
DC, wait 1 minute
and switch on again.
B
209
Detection of hardware de-
tection failed: AC relay
board
The data saved on the AC relay board is erro-
neous.
Disconnect AC and
DC, wait 1 minute
and switch on again.
B
216
Protect. shutdown HW -
overvoltage DC link halves
One of the two DC link halves has exceeded
the maximum value. Shutdown occurs by way
of HW-detection and TripZone shutdown.
Disconnect the AC
and DC supply. Wait
1 minute and switch
back on.
B
217
Protect. shutdown HW - 24V
supply voltage
The supply voltage in the device has exceeded
its max. permitted value. Shutdown occurs by
way of HW-detection and TripZone shutdown.
Disconnect the AC
and DC supply. Wait
1 minute and switch
back on.
B
224
External limitation
This is a relative specification of the desired
active power adjustment.
-
-
226
The inverter is disconnected
from the grid manually
The inverter can be disconnected from the grid
manually after logging in via the WebGui or
the button on the housing. This message then
appears.
Switch on the grid
by pressing the
function button for
a long time (> 5 sec)
[Chapter 9.6.1] or
activate the grid
connection using
the web interface
symbol.
B