Siren on Time (08x#)
This option sets the duration of time that the siren will remain on after a fence
alarm occurs. After this time the siren will turn off for the Siren Off Time indicated
in the table. The siren will sound again if the alarm is still present after this off
time has passed.
The default is 3 Minutes. This may be the subject of local regulations to
stop an alarm causing undue disturbance to neighbours, etc.
Note: the Siren On Time will be cut short if the battery falls below the low
battery level
Siren Off Time (09x#)
This option sets the amount of time the siren will be off for after the Siren On
Time has expired. If an alarm is still present after this off time the siren will sound
again.
Siren Cycles (10x#)
This option sets the maximum number of times the siren will sound for the “on
time” if the alarm continues. This may be limited by local regulations to stop an
alarm causing undue disturbance to neighbours etc.
Note: This is the maximum number of cycles for 1 continuous alarm, intermittent
alarm events could cause more than this number of siren soundings.
The value is set directly. For example to 2 siren cycles enter: 1 0 2 #.
The default is 3, minimum is 1 and the maximum is 9.
Input Type (11x#)
The control inputs can be inverted.
Unless an input is used for a Gate switch, in which case it is always NC.
Input 2 Function (12x#)
This input cannot be configured to anyth
ing other than a ‘Gate’ input at this time.
Value
Time
0
10 Seconds
1
30 Seconds
2
1 Minute
3
2 Minutes
4
3 Minutes
5
4 Minutes
6
5 Minutes
7
6 Minutes
8
7 Minutes
9
8 Minutes
Value
Time
0
10 Seconds
1
1 Minute
2
2 Minute
3
5 Minutes
4
10 Minutes
5
20 Minutes
6
30 Minutes
7
40 Minutes
8
50 Minutes
9
60 Minutes
Value
Cycles
0
1
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
Value (x)
Input type
0
NO Normally
open
1
NC Normally
Closed