eNet radio dimming actuator 1-gang mini
Parameters
Setting options, Basic setting
Explanations
If scenes are recalled or
switching uses logic modules,
the switch-on brightness is ap-
proached using so-called soft
dimming (not configurable).
Dim down ramp
0 s … 24 h
Basic setting: 0 s
Time until reaching minimum
brightness. The light is
dimmed to minimum bright-
ness and then switched off.
Only applies to switch-off with
transmitters (short operation).
If scenes are recalled or
switching uses logic modules,
the system switches off dir-
ectly.
Run-on time
0 s … 24 h
Basic setting: 0 s
As soon as a run-on time has
been entered, the actuator will
no longer remain on perman-
ently, but only for the length of
the run-on time. The run-on
time is restarted if actuation is
repeated. This parameter is
directly connected to the
"Manual switch-off of run-on
time" parameter.
Note: The set time apply to
operation using radio transmit-
ters. The device is switched
immediately when the Prog
button is pressed.
Manual switch-off of the run-
on time
On, Off
Basic setting: Off
Allows manual switch-off of a
running run-on time. If the
parameter is switched off,
then a switch-off command
will also switch the actuator
on. Only visible if a run-on
time was set.
Operating hours
0...65535
Basic setting: Current value
The time is counted during
which the load is physically
switched on.
This parameter can be reset
to "0", for example after ex-
changing the load.
The Reset button is used to