15 Behavior of Outputs
87
Operating status
Relay output con-
troller K1
Relay output limit value
K2
Analog output
Initialization
Initialization phase after mains voltage – ON
(for approx. 10 seconds
)
Inactive
Inactive
0 mA,
0 V
Setup communication
During reading-writing of the configuration
(for approx. 5 seconds)
Inactive
Limit value monitoring
active
v
Scaled analog signal is out-
put
v
Standard operation
System in error-free state after initialization
phase
Setpoint value moni-
toring active
v
Monitoring of limit value
depending on configura-
tion
v
Scaled analog signal is out-
put
v
External error
Probe break, probe short circuit
(e.g. input 1)
Inactive
Configured error signal is
output
v
Configured error signal is
output
v