9 Configuration level
56
9.6
Analog/logic output
Parameters
Comment
Value range
(default setting in bold)
9.6.1
Function
This setting specifies the signal that should be output at the
analog output.
Measured value,
Setpoint value,
Logic output
Measured value:
The value measured at the analog input is output.
Setpoint value:
The setpoint value is output.
Logic output:
With this setting, the switching status of the relay output
controller K1 or limit value K2 is also output as a binary sig-
nal 0/10V.
The output now no longer functions as an analog output.
This is set in Chapter 9.6.6.
The relay outputs retain their switching function.
9.6.2
Signal type
4 to 20 mA
4 to 20 mA,
0 to 20 mA
2 to 10 V
0 to 10 V
0 to 20 mA
2 to 10 V
0 to 10 V
9.6.3
Scaling start
v
Figure in Chapter 9.6.7
-9999 to -200 to 9999
9.6.4
Scaling end
v
Figure in Chapter 9.6.7
-9999 to 800 to 9999
Summary of Contents for exTHERM-DR
Page 2: ...Operating overview...
Page 3: ......
Page 9: ...Content...
Page 16: ...3 Mounting 16 3 Mounting 3 1 Dimensions...
Page 42: ...7 ATEX ignition protection type e and t 42 7 2 1 Probe arrangement in the Ex area...
Page 63: ...9 Configuration level 63...
Page 86: ...15 Behavior of Outputs 86 15 Behavior of Outputs...
Page 89: ...16 Certificates 89 16 Certificates Examination certificate...
Page 90: ...16 Certificates 90...
Page 91: ...16 Certificates 91...
Page 92: ...16 Certificates 92...
Page 94: ...16 Certificates 94 IECEx...
Page 95: ...16 Certificates 95...
Page 96: ...16 Certificates 96...
Page 97: ...16 Certificates 97 Ex e and t...
Page 98: ...16 Certificates 98...
Page 99: ...16 Certificates 99...