7 Configuration level
20
7.1
C111 Analog inputs
Analog input
Remark
Setting range for AL:
(can be restricted via
the set-up)
Limits for
underrange /
overrange
001
Pt 100
DIN EN 60751
in 3-wire circuit
-1999 ... +9999°C
-205°C/ +855°C
006
Pt 1000
DIN EN 60751
in 3-wire circuit
-1999 ... +9999°C
-205°C/ +855°C
601
KTY11-6 PTC
Probe in 2-wire circuit
-1999 ... +9999°C
-55°C/ +155°C
003
Pt 100
DIN EN 60751
in 2-wire circuit
-1999 ... +9999°C
-205°C/ +855°C
005
Pt 1000
DIN EN 60751
in 2-wire circuit
-1999 ... +9999°C
-205°C/ +855°C
024
2x Pt 100 DIN
for differential value calculation
-1999 ... +9999°C
-205°C/ +855°C
The device can calculate a differential value of 2 RTD temperature probes Pt 100 in 2-wire
circuit.
The measuring input INP (terminals 22 and 21) detects the first temperature.
The second measuring input IN2 (terminals 21 and 20) detects the second temperature.
Setting range for ALD: -1999 ... 9999
k
ex-factory
H
The "direct" and "inverse" settings do not influence the switch-
ing behavior of relay K1 during differential value calculation.
Summary of Contents for B70.1170.0
Page 2: ...Bedien bersicht C111 oErr siehe Kapitel 7 Konfigurationsebene...
Page 35: ...7 Konfigurationsebene 33 2011 03 13...
Page 46: ...11 Zertifikat 2011 03 13 44 11 Zertifikat...
Page 56: ...15 Was ist wenn 2011 03 13 54...
Page 57: ...15 Was ist wenn 55 2011 03 13...
Page 58: ...15 Was ist wenn 2011 03 13 56...
Page 94: ...7 Configuration level 33 2011 03 13...
Page 105: ...11 Certificate 2011 03 13 44 11 Certificate...
Page 115: ...15 What to do if 2011 03 13 54...
Page 116: ...15 What to do if 55 2011 03 13...
Page 117: ...15 What to do if 2011 03 13 56...