269
11 Annex
11.1.4
Digital inputs/outputs
11.1.5
Relays
Number
Max. 12 (see connection diagram)
Input or output
Individually configurable as input or output
Input
Level
Logic level 0:
<
3.5 V; logic level 1:
>
10 V
Sampling rate
125 ms (max. counting frequency: 4 Hz)
Potential-free contact
R
ON
:
<
1 k
Ω
; R
OFF
:
>
50 k
Ω
(use of auxiliary voltage 24 V)
High-speed input
Usable inputs
1, 2 (see connection diagram)
Function
Counts each positive edge of the input signal
Max. counting frequency
12.5 kHz
Mark-to-space ratio
30 to 70 % (high-pulse
≥
30
μ
s, low-pulse
≥
30
μ
s)
Accuracy for
flow measurement
0.5 % of measured value; ambient temperature influence: 50 ppm/K
Output
Output signal
DC 0/24 V +10/-15 %; galvanically isolated
Current
Max. 40 mA per output, max. 100 mA in total (including auxiliary voltage supply
current)
Auxiliary voltage supply
Voltage
DC 24 V +10/-15 %
Current
Max. 100 mA (including digital outputs current)
Number
1 (see connection diagram)
Relay (changeover contact)
Switching capacity
3 A at AC 230 V or DC 30 V, resistive load
Contact life
30,000 switching operations at rated load