7 Configuration
7.18
Groups
The user can configure up to four groups each with a maximum of six analog channels and six digital
channels. During the configuration, the user specifies whether the channels in a group can only be
viewed, or also stored, and how data recording occurs (memory cycle, storage method).
Grouping channels offers the ability, for example,
•
To configure a separate group for each plant,
•
To create one group each for different memory cycles (e.g., record pressure values every 125 ms,
temperature values every 2 s) or
•
To record special plant statuses in a separate group (e.g., record certain channels with a faster mem-
ory cycle if limit values are exceeded).
NOTE!
To use batch reporting at least one group must be active.
7.18.1
Parameter
Device dialog box
Parameter
Parameter
Selection/settings
Description
Status
General settings of the group
Inactive
(default setting as from group 2)
The group data are neither displayed nor
saved.
Display only
The group data are displayed on the
screen.
Display/Save
(default setting for group 1)
The group data are displayed on the
screen and saved. The group data can
only be evaluated using a PC if they
have been saved.
Name
Use default text or enter other text.
Description of the group, with a max.
length of 15 characters. The description
is shown in the individual visualizations.