105
7 Configuration
Voltage 0 to 1 V
Voltage signal
Voltage -1 to +1 V
Voltage signal
Voltage 0 to 10 V
Voltage signal
Voltage -10 to +10 V
Voltage signal
Current 0 to 20 mA
Current signal
Default setting for analog input 1 to 3
Current 4 to 20 mA
Current signal
Temperature in-
put
In the case of a voltage/current signal, resistance/potentiometer, or resistance
transmitter, the measured value must be defined as a temperature to convert auto-
matically when changing the temperature unit.
No
Measured value is not a temperature.
Yes
Measured value is a temperature.
Unit
Measured value unit for voltage/current signal, resistance/potentiometer or resis-
tance transmitter
%
(Max. 5 characters)
The unit is displayed if the measured val-
ue is displayed in numerical form
Linearization
Available options and default settings depend on the measuring sensor selected.
Linear
Pt50
IEC 751: 2008
Pt100
IEC 751: 2008
Pt500
IEC 751: 2008
Pt1000
IEC 751: 2008
Pt100 JIS
JIS 1604
Pt50 GOST
GOST 6651-2009 A.2
Pt100 GOST
GOST 6651-2009 A.2
Cu50 GOST
GOST 6651-2009 A.3
Cu100 GOST
GOST 6651-2009 A.3
Ni100
DIN 43760:1987-09
Ni100 GOST
GOST 6651-2009 A.5
Fe-CuNi L
DIN 43710:1985-12
Fe-CuNi J
DIN EN 60584-1:2014
Cu_CuNi U
DIN 43710:1985-12
Cu-CuNi T
DIN EN 60584-1:2014
NiCr-Ni K
DIN EN 60584-1:2014
NiCr-CuNi E
DIN EN 60584-1:2014
NiCrSI-NiSi N
DIN EN 60584-1:2014
Pt10Rh-Pt S
DIN EN 60584-1:2014
Pt13Rh-Pt R
DIN EN 60584-1:2014
Pt30Rh-Pt6Rh B
DIN EN 60584-1:2014
W5Re-W26Re C
ASTM E230M-11
W3Re-W25Re D
ASTM E1751M-09
W5Re-W20Re A1
GOST R 8.585-2001
Chromel®-Copel® L
GOST R 8.585-2001
Chromel®-Alumel®
GOST R 8.585-2001
Platinel II
Parameter
Selection/settings
Description
?