7 Configuration
106
Customer-specific 1 to 4
Customer-specific linearization using
grid points (pairs of values) or 4th order
polynomial
Resistance mea-
suring range
Measuring range for resistance/potentiometer and for customer-specific lineariza-
tion with RTD temperature probe
0 to 4000
Ω
0 to 400
Ω
Measuring range
start
-99999 to +99999
(Default setting depends on sensor and
linearization.)
Lower limit of measuring range (for volt-
age/current signal, resistance/potenti-
ometer, or resistance transmitter)
If the measured value is below the lower
limit, "<<<<<" (out of range) is shown for
a numerical display.
Measuring range
end
-99999 to +99999
(Default setting depends on sensor and
linearization.)
Upper limit of measuring range (for volt-
age/current signal, resistor/potentiome-
ter, or resistance transmitter)
If the measured value is above the upper
limit, ">>>>>" (out of range) is shown for
a numerical display.
Scaling
start
-99999 to +99999
(Default setting depends on sensor and
linearization.)
Lower limit of measuring range or display
range (depending on sensor and linear-
ization)
Scale
end
-99999 to +99999
(Default setting depends on sensor and
linearization.)
Upper limit of measuring range or display
range (depending on sensor and linear-
ization)
Decimal places
Number of pre-decimal and decimal places for the numerical display of the mea-
sured value
Even if the number of decimal places is fixed, the format is automatically changed
if needed in order to display all digits before the decimal point.
Auto
Automatic
XXXXXp
No decimal place
XXXXpX
One decimal place
XXXpXX
Two decimal places
XXpXXX
Three decimal places
XpXXXX
Four decimal places
Offset
-99999 to
0
to +99999
Correction value
Filter time con-
stant
0 s to
1 s
to 100 s
Time constant for adjusting the digital in-
put filter (0 s = filter off)
Compensation
Selection of cold junction (for thermocouple)
Internal Pt100
Internal Pt100 temperature probe
External constant
Constant cold junction temperature
Ext. reference
temperature
-30 to
0
to +85
Cold junction temperature (for thermo-
couple and constant cold junction tem-
perature)
Parameter
Selection/settings
Description
?
?
?
?
?
?