7 Configuration
118
Device dialog box
Parameter
Alarm/Event list
All events and their time of occurrence are added to the event list. If the event is an alarm, newly occur-
ring alarms and their time of occurrence are additionally added to the alarm list. If an alarm is made in-
active, it is removed from the alarm list and the time of removal is added to the event list.
Parameter
Selection/settings
Description
Activation
Inactive
Signal monitoring is inactive.
Active
Signal monitoring is active.
Alarm/Event list
Inactive (signal only)
In the event of an alarm, only the alarm
signal is activated.
Event
The alarm/event text is entered in the
event list.
Alarm/event
The alarm/event text is entered in the
alarm list and the event list. The collec-
tive alarm is activated and the text of the
last alarm to occur is displayed in the sta-
tus bar.
Alarm active at
High (1)
Alarm at high level (1)
Low (0)
Alarm at low level (0)
Alarm/Event text
Use default text or enter other text.
Text entered in the alarm and event list
and displayed in the status bar.
Alarm delay
0 s
to 32767 s
Delay time for alarm signal activation
Alarm suppres-
sion
Digital selector
No selection
The selected digital signal (high-active)
prevents the alarm signal being activat-
ed.
?
?
?