JMA-9100/7100 Installation Manual > 4.INITIAL SETTING > 4.1 GYRO INTERFACE SETTING
4
-
5
4
4.1.2
NMEA Input setting
Sentences HDT and THS are effective.
The baud rate can be selected from either 4800, 9600, 19200, or 38400.
Data must be updated within 60 ms. The sensor which outputs updated data with
an interval longer than 60 ms cannot be used. (An error is indicated)
Procedures
1)
To activate NMEA Input, set S2-6 at [ON].
2)
Set the baud rate for S2-7,8 in accordance with the heading sensor signal
output specifications.
3)
Make sure that the short plug of TB108 and 109 is located in the opposite
position of the standard position printed on the board. If it is inserted in the
default position (1-2), change it to the position between 2 and 3 as shown in
Table4-2
:
Gyro and Log Select Switches (S2 Dip Switch)
S2 SETTING TABLE
1
2
3
4
5
6
7
8
OTH
E
R SETTING
LOG ALARM
ON
OFF
GYRO SIMULATOR
ON
OFF
LOG SIMULATOR
ON
OFF
N.A.
Don't care
any
GYRO ALARM TIME
5s
ON
0.2s
OFF
HEADING SENSOR SOURCE
NMEA(HDT/THS)
ON
GYRO SIGNAL
OFF
NMEA BAUDRATE SETTING
4800
OFF
OFF
9600
ON
OFF
19200
OFF
ON
38400
ON
ON
Summary of Contents for JMA-7122-6XA
Page 2: ......
Page 8: ......
Page 22: ......
Page 24: ......
Page 42: ...1 18 JMA 9100 7100 Installation Manual 1 EQUIPMENT COMPOSITION 1 2 LIST OF CIRCUITS ...
Page 80: ...2 36 JMA 9100 7100 Installation Manual 2 INSTALLATION OF SCANNER UNIT 2 4 PRECAUTIONS ...
Page 128: ......
Page 222: ......
Page 224: ...6 2 JMA 9100 7100 Installation Manual 6 Appendix 6 1 EXTERIOR DRAWING Fig 6 1 NKE 1139 ...
Page 315: ......