background image

11

139472_Rev_B   8.28.12

Venting through a Masonry Fireplace

1.  Measure height of the chimney to fireplace opening.  

Determine if both the intake and exhaust will be 

extended to the top of the chimney. In Canada, both 

liners must extend the full length of the chimney 

and be connected to both the unit and the termina-

tion kit.

2.  Cut the appropriate lengths of flex duct for both the 

intake and exhaust. Label both ends of the Exhaust 

duct.

3.  Follow the manufacturer’s instructions to attach the 

ends of the duct(s) to the chimney termination kit as 

appropriate.

4.  Drop the liners down the chimney from the top and 

rest the termination kit atop the chimney.

5.  Seal the chimney termination kit to the top of the 

chimney flue with high temperature sealant.

6.  Secure the appropriate direct vent cap to the termi

-

nation kit.

7.  Inside the fireplace, fully extend the duct and trim 

any excess so that the ends hang approximately 15” 

from the floor of the fireplace.

8.  If the Intake duct is not attached to the chimney 

termination kit: 

  A.  The Air Intake flex pipe must extend at least up 

into the first flue tile.

  B.  The flue must be permanently sealed-off from the 

living area.

  C.  A direct vent cap is required to allow fresh air into 

the chimney flue and ultimately into the intake duct 

to the insert.

9.  Compress the ducts so that they are hanging above 

the height of the fireplace opening and are out of the 

way.

10.  Position the insert without surround panels half-

way inside the fireplace and attach duct you labelled 

Exhaust to the Exhaust collar on the insert. Both 

Intake and Exhaust collars are labelled.

11.  Secure the ducts to the collars with sheet metal 

screws or hose clamps.  No silicone or sealant is 

required.

12.  Once the gas line is installed, carefully push the unit 

inside the fireplace.

WARNING: FAILURE TO POSITION THE PARTS IN AC-

CORDANCE WITH THIS DIAGRAM OR FAILURE TO USE 

ONLY PARTS SPECIFICALLY APPROVED WITH THIS 

APPLIANCE MAY RESULT IN PROPERTY DAMAGE OR 

PERSONAL INJURY.

Figure 8.  Masonry Fireplace Venting Configuration.  

CANADA:  Air intake must connect to chimney cap. 

 

Listed, Standard 

or High-Wind 

Termination Cap

Maintain proper 

clearance to Mantel 

and Trim.  

See pages 8-9.

Sealed Chimney 

Cap Anchor Plate

In the U.S., the Air 

Intake pipe must 

extend through the 

damper and into 

the first chimney 

flue.

Exhaust 

Air 

Intake

The flue must be per-

manently sealed-off 

from the living area 

if the Air Intake pipe 

does not connect di-

rectly to a Direct Vent 

Termination at the top 

of the chimney.

Listed Flexible 

Gas Liners  

Max. Height 40 ft.

Min. Height 10 ft.

IMPORTANT NOTICE: 

INSTALLATION OF A HIGH-WIND TERMINATION CAP 

IS RECOMMENDED FOR ALL IPI APPLIANCES. IF USING 

SIMPSON DURA-VENT, AN ADDITIONAL WIND SCREEN 

#46DVA-VWG IS ALSO RECOMMENDED.

Summary of Contents for Scan 45i TSI

Page 1: ...aucum interrupteur Ne pas vous servir des t l phones se trou vant dans le b timent o vous trouvez Appelez imm diatement votre fournis seur de gaz depuis un voisin Suivez les instructions du fournisseu...

Page 2: ...d Installation shall be in strict compliance with the manufacturer s instructions A copy of the installation instructions must remain with the appliance or equipment at the completion of the installat...

Page 3: ...Starfire Glass Embers or Tumbled Stone burner media is packaged separately from the insert firebox Figure 1 Pull each Trunk Latch down to disengage it from the Glass Frame Glass Frame Latch Locations...

Page 4: ...s fireplace in sert has been tested and listed as a direct vent gas fireplace heater and listed to ANSI Z21 88 2009 CSA 2 33 2009 CAN CGA 2 17 M91 and CSA P 4 01 2 for Canada Starfire Glass Ember Kit...

Page 5: ...the codes have been established in CAN CGA B149 Fuel Installation Code Installer l appareil selon les codes ou reglements locaux ou en l absence de tels reglements selon les Codes d installation CAN...

Page 6: ...burns or clothing ignition Enfants et adultes doivent tre avertis des dangers des temp ratures de surface lev es et devraient rester l cart pour viter les br lures ou l inflammation des v tements Youn...

Page 7: ...ials Figure 2 Firebox dimensions Leg Leveling Bracket Note Two right and left brackets are factory installed The brackets allow the insert to be raised up to 2 1 2 off of the hearth Also note that use...

Page 8: ...imum 18 forward of the firebox glass panel Raised Hearth A raised hearth that is at least 6 high requires a non combustible hearth that extends a minimum 12 from the fireplace glass and and is a minim...

Page 9: ...Figure 5 Baseline Mantel and Trim clearance requirements The insert is raised 2 on the leveling brackets Leg Leveler Bolts and Brackets This feature enables greater installation flexibility beyond el...

Page 10: ...3 M99 TEST METHODS AND RESULTING ITS WHI PRODUCT CERTIFICATION THE CODE AUTHORITY HAVING JURISDICTION MUST BE CONSULTED PRIOR TO PROCEEDING WITH THIS INSTALLATION METHOD Vent Guidelines All vent compo...

Page 11: ...ct to the insert 9 Compress the ducts so that they are hanging above the height of the fireplace opening and are out of the way 10 Position the insert without surround panels half way inside the firep...

Page 12: ...ESULTING ITS WHI PRODUCT CERTIFICATION THE CODE AUTHORITY HAVING JURISDICTION MUST BE CONSULTED PRIOR TO PROCEEDING WITH THIS INSTALLATION METHOD Figure 9 Venting through prefabricated fireplace chimn...

Page 13: ...is still required to allow fresh air into the chimney flue and ultimately into the intake flex and insert D Attach the Fireplace Conversion Notice to the back of the fireplace if appropriate 9 Surrou...

Page 14: ...ARY MANIFOLD PRESSURES inches water column MIN MAX NATURAL GAS 1 6 WC 3 5 WC PROPANE 5 3 WC 11 0 WC ALWAYS TEST PRESSURE WITH THE VALVE REGULATOR ADJUSTED TO THE HIGHEST SETTING Figure 11 Gas connecti...

Page 15: ...ilot rectification and or frequent burner outages Little variation in flame picture between HI and LO regulator settings Insufficient gas to support more than one ap pliance causing nuisance outages o...

Page 16: ...TABLIS DANS LES IN STRUCTIONS DE PROPRIETAIRE PROVISIONNEES AVEC L EQUIPEMENT Conversion Kit LP 157249 NG 157250 Tools required 1 2 13 mm open end wrench or deep well socket Torx T20 driver 1 4 nut dr...

Page 17: ...ould not be able to move to the right or left 10 Replace the variable regulator on the gas control valve Remove the TruStart switch faceplate and move the assembly out of the way to access the regulat...

Page 18: ...aller and applied to the appli ance at the time of the conversion See fig 19 Derating procedure 1 Turn off gas supply to the appliance and disconnect from electrical power source 2 Remove the Glass Fr...

Page 19: ...ing the air shutter will generate a flame that is blue and transparent or an anemic flame This flame is generally more efficient but not very attractive We recommend the following settings for the Sca...

Page 20: ...shutter See figs 14 and 15 pages 16 17 4 Use a 10 mm socket to remove the left and right burner bracket nuts Remove the Burner Bracket from the firebox See fig 23 5 Bend the two upper rear tabs down...

Page 21: ...ure 26 Install Glass Embers Tumbled Stones Kit 157245 NOTE Install the optional Reflective Glass Panels before installing the stones Spread the stones evenly around the burner media tray CAUTION Take...

Page 22: ...mote Control connections GREEN GRAY The optional J tul Remote Control can be used with the Scan 45i TSI however the receiver must be installed outside of the firebox cabinet If there is no room for it...

Page 23: ...mable Backing Plate Front Assembly Riser Bar Leveling Brackets Standard Ventilated Control Door Optional Full Panel Control Door NOTE THE OPTIONAL FULL PANEL CONTROL DOOR MAY ONLY BE USED IN CONJUNCTI...

Page 24: ...r remote calls for heat the PREHEAT lamp will indicate Draw Collar warm up Pilot ignition occurs after approximately two to three minutes or when the vent is sufficiently heated to induce draft follow...

Page 25: ...dy not lifting or float ing The flame should be blue in color around the pilot hood with traces of yellow toward the outer edges It is important that the pilot flame engulf the top 1 8 of the flame re...

Page 26: ...ems 22 and 24 fig 39 on page 27 Use four AA batteries noting the polarity indicated on the box Glass Care Moisturecondensationisanormaloccurrencewithgasappli ancesandparticulateaccumulationmayappearon...

Page 27: ...onnectors 3 8 O D x 24 21 223953 Valve Bracket 22 22410792 Heat Shield Battery Box 23 117975 Wing Nut M6 Zinc 24 22426292 Battery Holder w cover 4 AA 25 223901 Heat Shield Valve 26 222280 Gasket Drop...

Page 28: ...0 F No Part Number Description 1 117917 Screw HWH SMA 8 x 1 2 SL Blk Oxide 2 222799 Blower Bracket 3 222072 Blower TransFlow 12 Cage 120 CFM No Part Number Description 1 117917 Screw HWH SMA 8 x 1 2 S...

Page 29: ...H WH M 1 3 2 4 5 6 7 8 9 10 GY GN GN BK BK BK TAN TAN BK WH BK WH BL GN BK BK BK RD BK RD BK RD BK GN YL GN BK YL GN GN OR GN TAN 13 12 TAN WH 11 14 BK BK BK WH BK TAN TAN TAN TAN NOTE Circled numbers...

Page 30: ...osts associated with the repair of gas controls plumbing burners log set or sheet metal firebox beyond the warranty period 5 Damage caused by unauthorized modification use or repair 6 Damage to enamel...

Page 31: ...Never use tools If the knob will not turn by hand do not try to repair it Call a qualified technician Force or attempted repair may result in a fire or explosion D Do not use this appliance if any pa...

Page 32: ...lation it is important that these instructions be carefully read and understood J tul maintains a policy of continual product development Consequently products may differ in specification color or typ...

Reviews: