8
Typical Wiring Diagram
SM-1700 SERIES ACTUATORS WITH A BUILT-IN AD-8130 AMPLIFIER
(120/240 Vac, Single Phase, 50-60 Hz)
Notes:
1. All references to actuator output shaft rotation are as viewed facing the actuator output shaft.
2. An increasing command signal will result in CW rotation of the actuator output shaft.
3. The torque limit switches are factory set to trip if the torque exceeds the actuator rating.
Do not adjust these trip points.
4. Shielded wire is required for command and position feedback signal wiring.
5. Comand signal input:
4 to 20 mA into a 200 ohm impedance
0 to 5 or 0 to 10 Vdc into a 100,000 ohm impedance
6. The EC-10852 is for use with the AD-8130 servo amplifier with LVDT (voltage feedback).
The EC-10852 is used as the HI and LO trim for the AD-8130. The AD-8130 is factory set
for operation with the EC-10852. CAUTION: It is important not to adjust the HI and LO trim
on the AD-8130, which are torque sealed at the factory. For specific Setup information and
calibration, refer to the wiring diagram supplied with your unit. This option is not shown in
the above diagram.
Refer to IM-0607 for complete information on the AD-8130 servo AMPLIFIER.
Due to wide variations
in terminal numbering
of actuator products, actual
wiring should follow the print
supplied with the actuator
.
Summary of Contents for SM-1715
Page 23: ...23...