b) Configuration with fireplace combustion air inlet communicating with the installation room.
The fireplace can work by taking the combustion air from the installation room. In this configuration it is mandatory to make an opening in
the installation room (minimum Ø200 mm) (1), communicating with the outside environment (positioned on the cladding interior or exterior),
guaranteeing a proper intake of combustion air such that it does not depressurise the installation room.
The opening in the installation room is mandatory in this configuration.
Make an opening (minimum 600 cm
2
) in the upper part of the cladding (2) to allow the heat to escape/heat recovery that forms inside the
cladding and an opening (minimum 600 cm
2
) in the lower part of the cladding (3) for the convective circulation of the cladding air.
The coating top and lower parts openings are mandatory.
It is mandatory to carry out an inspection opening on the cladding (4) for access to the part of the hydraulic connections and the
inspection of the flue gas pass.
4
2
3
1
2
3
1
Combustion air
opening positioned on
the cladding interior
Combustion air
opening positioned on
the cladding exterior