5834853-YIM-B-0320
Johnson Controls Ducted Systems
59
Troubleshooting
Troubleshooting of components may require opening
the electrical control box with the power connected to
the unit.
Use extreme care when working with live
circuits!
Check the unit nameplate for the correct line
voltage and set the voltmeter to the correct range before
making any connections with line terminals.
When not necessary, shut off all electric power to the
unit prior to any of the following maintenance
procedures so as to prevent personal injury.
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation, which could cause injury to person
and/or damage unit components. Verify proper
operation after servicing.
The furnace may shut down on a high temperature
condition during the procedure. If this occurs, the UCB
energize the supply air blower motor until the high
temperature limit has reset. Caution should be used at
all times as the supply air blower may energize
regardless of the room thermostat fan switch position.
Table 19: ZZ07 Charging Table
Air Flow
Indoor Db/Wb
Outdoor DB
Suction P
Suction Temp.
Liquid P
Liquid Temp.
Delta T Db
Compr. amps
300 Cfm/Ton
80/62
75
132
70
283
84
-24
11.1
85
135
66
329
94
-25
12.6
95
137
62
375
104
-25
14.1
300 Cfm/Ton
80/67
75
133
69
282
85
-25
10.9
85
138
66
330
95
-24
12.5
95
143
63
378
104
-22
14.2
300 Cfm/Ton
80/72
75
133
69
282
86
-25
10.7
85
141
66
331
96
-22
12.5
95
148
64
381
105
-20
14.3
300 Cfm/Ton
75/62
75
127
66
281
83
-22
11.1
85
130
62
328
93
-22
12.6
95
134
59
375
103
-22
14.1
400 Cfm/Ton
80/62
75
137
73
285
84
-22
11.3
85
141
71
331
94
-21
12.7
95
145
69
378
104
-21
14.2
400 Cfm/Ton
80/67
75
138
72
286
85
-21
11.2
85
143
70
333
95
-20
12.7
95
148
68
379
105
-19
14.2
400 Cfm/Ton
80/72
75
139
72
287
86
-21
11.1
85
145
69
334
96
-19
12.7
95
152
67
381
106
-18
14.3
400 Cfm/Ton
75/62
75
132
69
283
84
-19
11.2
85
136
67
329
94
-19
12.7
95
140
65
376
103
-18
14.1