5834853-YIM-B-0320
24
Johnson Controls Ducted Systems
14
(12.5)
208-3-60 19.6 136
31
19.6 136
31
5.8
9.9
1.1
None
-
-
-
59.8
60
70
63 367
62
70
80
66 377
11725 12
1
33.3
59.8
60
70
63 367
62
70
80
66 377
12525 18.6
1
51.6
76.9
80
80
71 367
79.6
80
80
73 377
13225 24
1
66.6
95.6
100
100
88 367
98.4
100
100
91 377
14225 31.8
2
88.3
122.8
125
125
113 367 125.5
150
150
115 377
230-3-60 19.6 136
31
19.6 136
31
5.2
9.4
1
None
-
-
-
58.7
60
70
62 372
60.7
70
80
64 376
11725 16
1
38.5
59.9
60
70
62 372
62.4
70
80
64 376
12525 24.8
1
59.7
86.4
90
90
79 372
88.9
90
90
82 376
13225 32
1
77
108
110
110
99 372 110.5
125
125
102 376
14225 42.4
2
102
139.3
150
150
128 372 141.8
150
150
130 376
460-3-60
8.2 66.1
13
8.2 66.1
13
2.9
4.7
0.5
None
-
-
-
26.1
30
30
28 184
27.1
30
30
29 186
11746 16.5
1
19.8
30.6
35
35
28 184
31.9
35
35
29 186
12846 27.8
1
33.4
47.6
50
50
44 184
48.9
50
50
45 186
13346 33
1
39.7
55.5
60
60
51 184
56.8
60
60
52 186
14246 41.7
2
50.2
68.6
70
70
63 184
69.9
70
70
64 186
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed
electric heat kits may exceed the factory installed disconnect amperage rating.
ZZ07-14 Medium Static Indoor Blower - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Nominal
Unit
Voltage
Compressor 1
Compressor 2
OD
Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
Electric Heat
Field Installed Kit
2EK045*
MCA
1
(Amps)
Min
Fuse
2
/
Breaker
3
Size
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
Min
Discon-
nect
Rating
4
MCA
1
w/Pwr
Exh
(Amps)
Min
Fuse
2
/
Breaker
3
Size
w/
Pwr Exh
(Amps)
Max
Fuse
2
/
Breaker
3
Size
w/
Pwr Exh
(Amps)
Min
Discon-
nect
Rating
4
/
Pwr Exh
RLA LRA MCC RLA LRA MCC
Model kW Stages Amps
FLA LRA
FLA LRA
Summary of Contents for ZZ Series
Page 10: ...5834853 YIM B 0320 10 Johnson Controls Ducted Systems Figure 10 ZZE07 08 Unit Dimension...
Page 11: ...5834853 YIM B 0320 Johnson Controls Ducted Systems 11 Figure 11 ZZ09 12 Unit Dimensions...
Page 12: ...5834853 YIM B 0320 12 Johnson Controls Ducted Systems Figure 12 ZZ14 Unit Dimensions...