Johnson Controls Ducted Systems
Table 15: Additional Static Resistance - ZZ08-14
Model
Size
Tons
CFM Cooling Only
1
Economizer
2
3
4” Filter
2
Electric Heat kW
2
6/6.5 9.2/10.5/11 13.8/14/16 16/16.5/17 23 24.8/25.5/27.8 32/33/34 41.7/42.4
ZZ
08
(7.5),
09
(8.5),
12
(10.0),
14
(12.5)
2200
0.04
0.11
---
---
---
---
0.07
---
0.09
0.10
0.12
2600
0.06
0.13
---
---
---
---
0.09
---
0.11
0.12
0.15
3000
0.10
0.17
---
---
---
---
0.12
---
0.14
0.15
0.19
3400
0.13
0.20
---
---
---
---
0.15
---
0.18
0.19
0.23
4800
0.22
0.38
---
---
---
---
0.30
---
0.34
0.35
0.41
5200
0.24
0.43
---
---
---
---
0.35
---
0.39
0.41
0.47
5600
0.26
0.46
---
---
---
---
0.41
---
0.45
0.47
0.54
6000
0.28
0.50
---
---
---
---
0.48
---
0.52
0.54
0.60
1. Add these values to the available static resistance in the respective Blower Performance Tables.
2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is
less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Table 16: Additional Static Resistance - ZZ07
Model
Size
(Tons)
CFM
Cooling Only
1
Economizer
2
3
4” Filter
2
Electric Heat kW
2
6/6.5 10.5/11 14/16 16/16.5/17 24.8/25.5/27.8 32/33/34 41.7/42.4
ZZ
07 (6.0)
1800
0.23
0.11
---
0.03
0.03
0.05
---
---
---
---
2000
0.28
0.13
---
0.04
0.04
0.06
---
---
---
---
2200
0.32
0.15
---
0.06
0.06
0.07
---
---
---
---
2400
0.37
0.17
---
0.07
0.07
0.08
---
---
---
---
2600
0.38
0.20
---
0.08
0.08
0.09
---
---
---
---
2800
0.41
0.24
---
0.09
0.09
0.10
---
---
---
---
3000
0.45
0.29
---
0.11
0.11
0.12
---
---
---
---
1. Add these values to the available static resistance in the respective Blower Performance Tables.
2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct
is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.