5834853-YIM-B-0320
30
Johnson Controls Ducted Systems
14
(12.5)
208-3-60 19.6 136
31
19.6 136
31
5.8
13.5
1.1
8.6
None
-
-
-
67.7
70
80
72 401
69.9
70
80
75 411
11725 12
1
33.3
67.7
70
80
72 401
69.9
70
80
75 411
12525 18.6
1
51.6
86.8
90
90
80 401
89.5
90
90
82 411
13225 24
1
66.6
105.5
110
110
97 401 108.3
110
110
100 411
14225 31.8
2
88.3
132.6
150
150
122 401 135.4
150
150
125 411
230-3-60 19.6 136
31
19.6 136
31
5.2
13.4
1
8.6
None
-
-
-
67
70
80
71 397
69
70
80
74 402
11725 16
1
38.5
70.3
80
80
71 397
72.8
80
80
74 402
12525 24.8
1
59.7
96.8
100
100
89 397
99.3
100
100
91 402
13225 32
1
77
118.4
125
125
109 397 120.9
125
125
111 402
14225 42.4
2
102
149.6
150
150
138 397 152.1
175
175
140 402
460-3-60
8.2 66.1
13
8.2 66.1
13
2.9
6.7
0.5
8.6
None
-
-
-
30.3
35
35
32 196
31.3
35
35
34 199
11746 16.5
1
19.8
35.8
40
40
33 196
37.1
40
40
34 199
12846 27.8
1
33.4
52.8
60
60
49 196
54.1
60
60
50 199
13346 33
1
39.7
60.7
70
70
56 196
61.9
70
70
57 199
14246 41.7
2
50.2
73.8
80
80
68 196
75.1
80
80
69 199
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed
electric heat kits may exceed the factory installed disconnect amperage rating.
ZZ07-14 Hi Static Indoor Blower - With Powered Convenience Outlet (Continued)
Size
(Tons)
Nominal
Unit
Voltage
Compressor 1
Compressor 2
OD
Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
Electric Heat
Field Installed Kit
2EK045*
MCA
1
(Amps)
Min
Fuse
2
/
Breaker
3
Size
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
Min
Discon-
nect
Rating
4
MCA
1
w/Pwr
Exh
(Amps)
Min
Fuse
2
/
Breaker
3
Size
w/
Pwr Exh
(Amps)
Max
Fuse
2
/
Breaker
3
Size
w/
Pwr Exh
(Amps)
Min
Discon-
nect
Rating
4
/
Pwr Exh
RLA LRA MCC RLA LRA MCC
Model kW Stages Amps
FLA LRA
FLA LRA
Summary of Contents for ZZ Series