70
P5417009-rev.6
(b) Operate the compressor in the cooling mode and charge the additional refrigerant from the access
port of the liquid stop valve. An acceptable error must fall within 1.1 lbs (0.5 kg). At this time, keep
the liquid stop valve slightly open.
(c) After the refrigerant is charged, fully open the liquid stop valve and the gas stop valve.
(d) Carefully calculate any additional refrigerant quantity for charging. If the quantity of additional
refrigerant is not correct, it might cause a compressor failure. The additional refrigerant must be
charged in a liquid condition.
(e) Refrigerant charge from the access port on the gas stop valve can lead to compressor failure.
Be sure to charge refrigerant from the access port on the liquid stop valve.
Charge the correct refrigerant
quantity according to Table 8.1.
If not, a compressor may be
damaged due to an excess or
insufficient refrigerant charge.
Refrigerant charge from access
port of gas stop valve may lead
to compressor failure. Be sure
to charge refrigerant from the
access port of liquid stop valve.
Insulate the liquid piping and
gas piping completely to avoid
decreasing of performance and
condensation on the surface of
the pipe.
Insulate the flare nut and union
of the piping connection with
insulation.
Check to ensure that there
is no gas leakage. If a large
refrigerant leakage occurs, it will
cause difficulty with breathing or
harmful gases would occur if a
fire was being used in the room.
Stop Valve
(for Low
Pressure Gas)
Stop Valve
(for Low
Pressure Gas)
Outdoor Unit C
Stop Valve
(for Liquid)
Manifold
Gauge
Vacuum Pump
Nitrogen Tank
(for Nitrogen Blow during Brazing
and Airtight Test)
Scale
Indoor Unit
Low Pressure Gas Line
Liquid Line
Multi-Kit
Insulation
[Cover the gas and liquid pipe with insulation.]
Refrigerant Cylinder
(R410A)
CH-Box
Stop Valve
(for High/Low
Pressure Gas)
Outdoor Unit B Outdoor Unit A
Stop Valve
(for High/Low
Pressure Gas)
Stop Valve
(for High/Low
Pressure Gas)
High/Low Pressure Gas Line
Stop Valve
(for Low
Pressure Gas)
Stop Valve
(for Liquid)
Stop Valve