P5417009-rev.6
55
Table 7.1 Electrical Characteristics and Recommended Wiring Size
(2) Electrical Characteristics
Note the following when selecting wiring:
●
Use the charts below to select appropriate sized breakers / fuses / overcurrent protection switches and
wiring in accordance with local codes.
●
Ensure communication cable is a minimum of AWG18 (0.82mm
2
), 2-Conductor, Stranded Copper.
Shielded cable must be considered for applications and routing in areas of high EMI and other sources
of potentially excessive electrical noise to reduce the potential for communication errors. When
shielded cable is applied, secure properly and terminate cable shield as required per Johnson Controls
guidelines. Plenum and riser ratings for communication cables must be considered per application and
local code requirements.
208/230V
Model
Outdoor Unit
Inverter 1 Inverter 2 INV Comp. 1 INV Comp. 2
Hz
Voltage
Max.
Min.
MCA
MOP
Max. Fuse
MOC
MOC
LRA
LRA
(Hz)
(V)
(V)
(V)
(A)
(A)
(A)
(A)
(A)
(A)
(A)
(H,Y)VAHR072B32S 60 208/230
253
188
29/26
40/40
40/40
22.6
-
50
-
(H,Y)VAHR096B32S 60 208/230
253
188
39/35
50/50
50/50
30.7
-
50
-
(H,Y)VAHR120B32S 60 208/230
253
188
46/42
60/50
60/50
20.2
20.2
54
54
(H,Y)VAHR144B32S 60 208/230
253
188
58/52
70/70
70/70
25.5
25.5
54
54
(H,Y)VAHR168B32S 60 208/230
253
188
65/59
80/80
80/80
28.6
28.6
50
50
(H,Y)VAHR192B32S 60 208/230
253
188
76/68
90/90
90/90
33.4
33.4
50
50
Model
Fan Motor 1 Fan Motor 2
Wiring Size
Output
Output
Power Supply
Wiring
Ground
Wiring
Communication
Cable
(kW)
(kW)
(AWG)
(AWG)
(AWG)
(H,Y)VAHR072B32S
0.75
-
10/10
10/10
18
(H,Y)VAHR096B32S
0.75
0.75
8/8
8/8
18
(H,Y)VAHR120B32S
0.75
0.75
6/6
6/6
18
(H,Y)VAHR144B32S
0.75
0.75
4/4
4/4
18
(H,Y)VAHR168B32S
0.75
0.75
4/4
4/4
18
(H,Y)VAHR192B32S
0.75
0.75
2/4
2/4
18
460V
Model
Outdoor Unit
Inverter 1 Inverter 2 INV Comp. 1 INV Comp. 2
Hz
Voltage
Max.
Min.
MCA
MOP
Max. Fuse
MOC
MOC
LRA
LRA
(Hz)
(V)
(V)
(V)
(A)
(A)
(A)
(A)
(A)
(A)
(A)
(H,Y)VAHR072B42S 60
460
506
414
15
20
20
11.5
-
47
-
(H,Y)VAHR096B42S 60
460
506
414
22
30
30
17.1
-
47
-
(H,Y)VAHR120B42S 60
460
506
414
24
30
30
10.4
10.4
32
32
(H,Y)VAHR144B42S 60
460
506
414
30
35
35
13.2
13.2
32
32
(H,Y)VAHR168B42S 60
460
506
414
34
40
40
14.8
14.8
47
47
(H,Y)VAHR192B42S 60
460
506
414
39
50
50
17.3
17.3
47
47
Model
Fan Motor 1 Fan Motor 2
Wiring Size
Output
Output
Power Supply
Wiring
Ground
Wiring
Communication
Cable
(kW)
(kW)
(AWG)
(AWG)
(AWG)
(H,Y)VAHR072B42S
0.75
-
14
14
18
(H,Y)VAHR096B42S
0.75
0.75
12
12
18
(H,Y)VAHR120B42S
0.75
0.75
12
12
18
(H,Y)VAHR144B42S
0.75
0.75
10
10
18
(H,Y)VAHR168B42S
0.75
0.75
8
8
18
(H,Y)VAHR192B42S
0.75
0.75
8
8
18
MCA: Minimum Circuit Ampacity (A)
MOP: Maximum Overcurrent Protective Device (A)
MOC: Maximum Operating Current (A)
LRA: Locked Rotor Ampacity (A)