P5417009-rev.6
i
Important Notice
●
Johnson Controls Inc. pursues a policy of continuing improvement in design and performance in its products.
As such, Johnson Controls Inc. reserves the right to make changes at any time without prior notice.
●
Johnson Controls Inc. cannot anticipate every possible circumstance that might involve a potential hazard.
●
This heat recovery air conditioning unit is designed for standard air conditioning applications only.
Do not use this unit for anything other than the purposes for which it was intended for.
●
The installer and system specialist shall safeguard against leakage in accordance with local codes.
No part of this manual may be reproduced in any way without the expressed written consent of Johnson
Controls Inc.
●
This heat recovery air conditioning unit will be operated and serviced in the United States of America and
comes with a full complement of the appropriate Safety, Danger, and Caution, Warnings.
●
If you have questions, please contact your distributor or contractor.
●
This manual provides common descriptions, basic and advanced information to maintain and service this
heat recovery air conditioning unit which you operate as well for other models.
● This heat recovery air conditioning unit has been designed for a specific temperature range. For optimum
performance and long life, operate this unit within the range limits according to the table below.
Temperature
Cooling Operation Range
Indoor
o
F WB
(
o
C WB)
59 (15) ~ 73 (23)
Outdoor
1, 2, 3, 6, 10
o
F DB
(
o
C DB)
23 (-5) ~ 122 (50)
with Snow Protection Hood
4, 6
o
F DB
(
o
C DB)
14 (-10) ~ 109 (43)
with Low Ambient Kit
5, 6, 8
o
F DB
(
o
C DB)
-10 (-23) ~ 109 (43)
Heating Operation Range
Indoor
o
F DB
(
o
C DB)
59 (15) ~ 80 (27)
Outdoor
7, 8, 9
o
F WB
(
o
C WB)
-13 (-25) ~ 59 (15)
Cooling & Heating
Operation Range
Cooling
Indoor
o
F WB
(
o
C WB)
59 (15) ~ 73 (23)
Outdoor
1, 2, 3, 6, 10
o
F DB
(
o
C DB)
23 (-5) ~ 75 (24)
with Snow Protection Hood
4, 6
o
F DB
(
o
C DB)
14 (-10) ~ 75 (24)
with Low Ambient Kit
5, 6, 8
o
F DB
(
o
C DB)
-10 (-23) ~ 75 (24)
Heating
Indoor
o
F DB
(
o
C DB)
59 (15) ~ 80 (27)
Outdoor
7, 10
o
F WB
(
o
C WB)
22 (-6) ~ 59 (15)
with Snow Protection Hood
4, 6
o
F WB
(
o
C WB)
12 (-11) ~ 59 (15)
with Low Ambient Kit
5, 6, 8
o
F WB
(
o
C WB)
-11 (-24) ~ 59 (15)