ISN TRANSMITTED DATA (CON'T)
TABLE 26 - DXST / ISN TRANSMITTED DATA (SECTION 1 UNIT, SYS 1, SYS 2) (CON'T)
ISN PAGE
CHARACTER
TYPE
DXST CHILLER DATA (UNIT, Sys 1, Sys 2)
P47
119
Digital
—
P48
120
Digital
—
P49
121
Digital
—
P50
122
Digital
Cooling Type: 0=Water, 1=Glycol
P51
123
Digital
Local / Remote Control Mode: 0=Local, 1=Re
-
mote
P52
124
Digital
Display Units Mode: 0=Imperial, 1=SI
P53
125
Digital
—
P54
126
Digital
—
P55
127
Digital
—
P56
128
Coded
*Sys 1 Operational Code
P57
129
Coded
*Sys 1 Fault Code
P58
130
Coded
*Sys 2 Operational Code
P59
131
Coded
* Sys 2 Fault Code
P60
132
Coded
Sys 1 Flash Tank Level (%)
P61
133
Coded
Sys 1 Condensor Fan Stage (0-6)
P62
134
Coded
Sys 2 Flash Tank Level (%)
P63
135
Coded
Sys 2 Condensor Fan Stage (0-6)
P64
136
Coded
Lead System Number
P65
137
Coded
Sys 1 & 2 Debug Code
P66
138-141
Analog
Local Leaving Chilled Liquid Setpoint
P67
142-145
Analog
Low Leaving Chilled Liquid Temp. Cutout
P68
146-149
Analog
Sys 1 Flash Tank Drain Valve % Open
P69
150-153
Analog
Sys 2 Flash Tank Drain Valve % Open
P70
154-157
Analog
Low Suction Pressure Cutout
P71
158-161
Analog
VSD DC Bus Voltage
P72
162-165
Analog
Remote Leaving Chilled Liquid Setpoint
P73
166-169
Analog
Sys 1 Discharge Superheat
P74
170-173
Analog
Cooling Range
P75
174-177
Analog
Sys 1 Discharge Superheat
P76
178-181
Analog
Sys 2 Suction Temp
P77
182-185
Analog
Sys 2 Discharge Temp.
P78
186-189
Analog
Sys 2 Suction Superheat
P79
190-193
Analog
Sys 2 Discharge Superheat
P80
194
Digital
—
P81
195
Digital
—
P82
196
Digital
—
P83
197
Digital
—
P84
198
Digital
—
* The operational and fault codes are defined in Tables 27 and 28 (Pages 283-285).