LOAD LIMITING CONTROL (CON'T)
Suction Pressure Load Limiting/Unloading
Suction pressure load limiting helps to protect the
evaporator from freezing. A system is permitted to load
normally as long as the Suction Pressure is above the
Suction Pressure 2 PSIG. Between
2 PSIG and the Cutout, loading is inhibited, even though
increased loading is required. Between the Suction
pressure Cutout and Suction Pressure Cutout – 10 PSIG,
forced unloading is performed every 2 seconds accord-
ing to TABLE 8 below. This situation would occur if
the suction pressure cutout transient override control
is in effect (See Low Suction Pressure Cutout, PAGE
213). The suction pressure cutout is programmed under
the Program key. The default Suction Pressure Cutout
is set at 24.0 PSIG.
TABLE 8 - SUCTION PRESSURE
LOAD LIMITING/UNLOADING
SUCTION PRESSURE
UN-
LOADING
Suction Pressure is between
2 PSIG
&
Suction Pressure Cutout
0 Hz
Suction Pressure Cutout- 1 PSIG
1 Hz
Suction Pressure Cutout- 2 PSIG
2 Hz
Suction Pressure Cutout- 3 PSIG
3 Hz
Suction Pressure Cutout- 4 PSIG
4 Hz
Suction Pressure Cutout- 5 PSIG
5 Hz
Suction Pressure Cutout- 6 PSIG
6 Hz
Suction Pressure Cutout- 7 PSIG
7 Hz
Suction Pressure Cutout- 8 PSIG
8 Hz
Suction Pressure Cutout- 9 PSIG
9 Hz
Suction Pressure Cutout- 10 PSIG
10 Hz
Suction pressure load limiting is active at start-up, to
only prevent loading of the compressors. Suction pres-
sure limit unloading will not occur until the system run
time reaches 5 minutes of operation to allow the system
to stabilize.
VSD Internal Ambient Temperature
Load Limiting
VSD Internal Ambient temperature limiting helps pre-
vent the unit from tripping on the high internal cabinet
temperature safety. A system is permitted to load nor-
mally as long as the VSD Internal Ambient is below the
VSD Internal Ambient Cutout – 3°F. Between VSD
Internal Ambient Cutout – 3°F and the VSD Internal
Ambient Cutout – 2°F, loading is inhibited, even though
increased loading is required. Between the VSD Internal
Ambient Cutout – 2°F and the VSD Internal Ambient
Cutout, forced unloading is performed every 2 seconds
according to TABLE 9 below. The VSD Internal Ambi-
ent Safety Cutout is 158°F.
TABLE 9 - VSD INTERNAL AMBIENT
LOAD LIMITING/UNLOADING
VSD INTERNAL AMBIENT
TEMPERATURE
UN-
LOADING
Internal Ambient Temp. is between
Cutout- 3ºF
&
Internal Ambient Cutout- 2ºF
0 Hz
Internal Ambient Cutout- 1.8ºF
1 Hz
Internal Ambient Cutout- 1.6ºF
2 Hz
Internal Ambient Cutout- 1.4ºF
3 Hz
Internal Ambient Cutout- 1.2ºF
4 Hz
Internal Ambient Cutout- 0ºF
5 Hz
Internal Ambient Cutout- 0.8ºF
6 Hz
Internal Ambient Cutout- 0.6ºF
7 Hz
Internal Ambient Cutout- 0.4ºF
8 Hz
Internal Ambient Cutout- 0.2ºF
9 Hz
Internal Ambient Cutout
10 Hz