108
JOHNSON CONTROLS
FORM 201.21-NM4 (616)
108
JOHNSON CONTROLS
TECHNICAL DATA
VIEW C-C
VIEW B-B
381
CONTROL ENTRY
76 WIDE X 292 HIGH
38
102
POWER ENTRY
254 WIDE X 330 HIGH
75
POWER ENTRY IS ON BOTTOM OF PANEL
VIEW A-A
2273
16
2241
C
C
B
B
Notes:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable
operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable air flow
patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high pressure safety cutout;
however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher
than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m; control panel end to wall - 1.2m; top - no
obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be higher than the unit.
DIMENSIONS - YCAV1739E/V
High Efficiency SI