JOHNSON CONTROLS
93
FORM 150.62-NM9 (709)
2
FIG. 8 –
LEAVING WATER TEMPERATURE CONTROL EXAMPLE
LEAVING CHILLED LIQUID CONTROL OVERRIDE
TO REDUCE CYCLING
To avoid compressor cycling the I/O Board will adjust
the setpoint upward temporarily. The last run time of the
system will be saved. If the last run time was greater than
5 minutes, no action is to be taken. If the last run time
for the lead system was less than 5 minutes, increase the
setpoint high limit according to the chart at right, with
a maximum value allowed of 50°F.
If adding the setpoint adjust value to the setpoint high
limit causes the setpoint high limit to be greater than
50°F, the setpoint high limit will be set to 50°F, and the
difference will be added to the setpoint low limit.
Once a system runs for greater than 5 minutes, the
setpoint adjust will be set back to 0. This will occur
while the system is still running.
Leaving Water Temp. Control – Compressor Staging
Setpoint = 46.0°F (7.8°C) Range = +/- 2°F(1.1°C)
30 sec.
control range
60 sec.
unloading
(no compressor staging)
loading
44.0°F
46.0°F
48.0°
(6.7°C)
(7.8°C)
(8.9°C)
Low Limit
Setpoint
High limit
LWT
FIG. 7 –
SETPOINT ADJUST
0
1
2
3
4
5
6
LAST RUN TIME OF LEAD SYSTEM (MINUTES)
SETPOINT ADJUST (DEG.
F)
6
5
4
3
2
1
0
RETURN CHILLED LIQUID CONTROL
(Can be used on Dual System 4, 5 & 6 Comp Units
Only)
Return chilled liquid control is based on staging the com-
pressors to match the cooling load. The chiller will be
fully loaded when the return water temperature is equal
to the Cooling Setpoint plus the Range. The chiller will
be totally unloaded (all compressors off) when the re-
turn water temperature is equal to the Cooling Setpoint.
(See sample in Table 18) At return water temperatures
between the Cooling, and Cooling Setpoint plus Range,
compressor loading and unloading will be determined
by the formulas in Table 19 or Table 20.
Return Chilled Liquid Control MUST
only be used when constant chilled liq
-
uid flow is ensured.
The
range
MUST always be pro
-
grammed to equal the temperature
drop across the evaporator when the
chiller is “fully loaded”. Otherwise,
chilled liquid temperature will over or
under shoot.
Normal loading will occur at intervals of 60 seconds ac-
cording to the temperatures determined by the formulas.
Unloading will occur at a rate of 30 seconds according to
the temperatures determined in the formulas.
The return chilled liquid setpoint is programmable from
40°F to 70°F (4.4°C to 21.1°C) in water chilling mode
and from 10°F to 70°F (-12.2°C to 21.1°C) in glycol
chilling mode. In both modes, the cooling range can be
from 4°F to 20°F (2.2° to 11.1°C).
LD07617A
Summary of Contents for YORK YCAL0043E Series
Page 21: ...JOHNSON CONTROLS 21 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 102: ...JOHNSON CONTROLS 102 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 123: ...JOHNSON CONTROLS 123 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 125: ...JOHNSON CONTROLS 125 FORM 150 62 NM9 709 4 ...
Page 127: ...JOHNSON CONTROLS 127 FORM 150 62 NM9 709 4 ...
Page 129: ...JOHNSON CONTROLS 129 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 131: ...JOHNSON CONTROLS 131 FORM 150 62 NM9 709 4 LD08855 035 21627 000 REV B ...
Page 133: ...JOHNSON CONTROLS 133 FORM 150 62 NM9 709 4 035 19213 106 REV C ...
Page 135: ...JOHNSON CONTROLS 135 FORM 150 62 NM9 709 4 ...
Page 137: ...JOHNSON CONTROLS 137 FORM 150 62 NM9 709 4 ...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 62 NM9 709 4 035 21628 000 REV B ...
Page 143: ...JOHNSON CONTROLS 143 FORM 150 62 NM9 709 4 035 19213 105 REV C ...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 62 NM9 709 4 ...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 62 NM9 709 4 ...
Page 149: ...JOHNSON CONTROLS 149 FORM 150 62 NM9 709 4 ...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 62 NM9 709 4 035 21625 000 REV B ...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 62 NM9 709 4 035 19213 104 REV C ...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 62 NM9 709 4 ...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 62 NM9 709 4 ...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 62 NM9 709 4 ...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 62 NM9 709 4 035 21626 000 REV B ...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 62 NM9 709 4 035 19213 103 REV C ...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 62 NM9 709 4 ...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 62 NM9 709 4 LD08833 ...
Page 169: ...JOHNSON CONTROLS 169 FORM 150 62 NM9 709 4 035 21610 104 REV ...
Page 171: ...JOHNSON CONTROLS 171 FORM 150 62 NM9 709 4 035 18150 102 REV D ...
Page 173: ...JOHNSON CONTROLS 173 FORM 150 62 NM9 709 4 ...
Page 175: ...JOHNSON CONTROLS 175 FORM 150 62 NM9 709 4 ...
Page 177: ...JOHNSON CONTROLS 177 FORM 150 62 NM9 709 4 035 21606 104 REV ...