JOHNSON CONTROLS
85
FORM 150.62-NM9 (709)
2
S Y S 1 S U C T S U P E R H E A T
S E T P O I N T = X X . X ° F
S Y S 2 S U C T S U P E R H E A T
S E T P O I N T = X X . X ° F
These messages only appear and are programmable
when EEV is selected as the expansion valve type in the
Service Mode. EEV must only be selected when an EEV
is installed. Superheat is programmable between 10°F -
15°F. A setpoint of 12°F - 15°F is recommended.
TABLE 15 –
PROGRAM KEY LIMITS AND DEFAULTS
PROGRAM VALUE
MODE
LOW LIMIT
HIGH LIMIT
DEFAULT
DISCHARGE PRESSURE CUTOUT
—
200 PSIG
399 PSIG
395 PSIG
13.8 BARG
27.5 BARG
27.2 BARG
SUCTION PRESSURE CUTOUT
WATER COOLING
44.0 PSIG
70.0 PSIG
44.0 PSIG
3.03 BARG
4.83 BARG
3.03 BARG
GLYCOL COOLING
20.0 PSIG
70.0 PSIG
44.0 PSIG
1.38 BARG
4.83 BARG
3.03 BARG
LOW AMBIENT TEMP. CUTOUT
STANDARD AMBIENT
25.0°F
60.0°F
25.0°F
-3.9°C
15.6°C
-3.9°C
LOW AMBIENT
0°F
60.0°F
25.0°F
-17.8°C
15.6°C
-3.9°C
LEAVING CHILLED LIQUID
WATER COOLING
—
—
36°F
2.2°C
TEMP. CUTOUT
GLYCOL COOLING
8.0°F
36.0°F
36.0°F
-13.3°C
2.2°C
2.2°C
ANTI-RECYCLE TIMER
—
300 SEC.
600 SEC.
600 SEC.
FAN CONTROL ON PRESSURE
—
225 PSIG
260 PSIG
240 PSIG
15.5 BARG
17.9 BARG
16.5 BARG
FAN DIFFERENTIAL OFF PRESSURE
—
50 PSIG
100 PSID*
80 PSID
3.45 BARG
6.89 BARG*
5.52 BARG
TOTAL NUMBER OF COMPRESSORS
SINGLE SYSTEM
2
3
3
TWO SYSTEMS
4
6
6
NUMBER OF FANS PER SYSTEM
YCAL0287 –
3
4
3
YCAL0377 ONLY
CURRENT FEEDBACK
UNIT/SYSTEM TRIP VOLTS
OPTION ENABLED
0.5
4.5
2
ONE PER UNIT
REMOTE UNIT ID
—
0
7
0
SYSTEM 1 SUPERHEAT SETPOINT
EEV
10.0°F
15.0°F
12.0°F
5.5°C
8.3°C
6.6°C
SYSTEM 2 SUPERHEAT SETPOINT
EEV
10.0°F
15.0°F
12.0°F
5.5°C
8.3°C
6.6°C
* The minimum discharge pressure allowed is 160 PSIG. The fan differential Off Pressure will be lowered to prevent going below 160 PSIG
based on where the fan control On Pressure is programmed.
Summary of Contents for YORK YCAL0043E Series
Page 21: ...JOHNSON CONTROLS 21 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 102: ...JOHNSON CONTROLS 102 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 123: ...JOHNSON CONTROLS 123 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 125: ...JOHNSON CONTROLS 125 FORM 150 62 NM9 709 4 ...
Page 127: ...JOHNSON CONTROLS 127 FORM 150 62 NM9 709 4 ...
Page 129: ...JOHNSON CONTROLS 129 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 131: ...JOHNSON CONTROLS 131 FORM 150 62 NM9 709 4 LD08855 035 21627 000 REV B ...
Page 133: ...JOHNSON CONTROLS 133 FORM 150 62 NM9 709 4 035 19213 106 REV C ...
Page 135: ...JOHNSON CONTROLS 135 FORM 150 62 NM9 709 4 ...
Page 137: ...JOHNSON CONTROLS 137 FORM 150 62 NM9 709 4 ...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 62 NM9 709 4 035 21628 000 REV B ...
Page 143: ...JOHNSON CONTROLS 143 FORM 150 62 NM9 709 4 035 19213 105 REV C ...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 62 NM9 709 4 ...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 62 NM9 709 4 ...
Page 149: ...JOHNSON CONTROLS 149 FORM 150 62 NM9 709 4 ...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 62 NM9 709 4 035 21625 000 REV B ...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 62 NM9 709 4 035 19213 104 REV C ...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 62 NM9 709 4 ...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 62 NM9 709 4 ...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 62 NM9 709 4 ...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 62 NM9 709 4 035 21626 000 REV B ...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 62 NM9 709 4 035 19213 103 REV C ...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 62 NM9 709 4 ...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 62 NM9 709 4 LD08833 ...
Page 169: ...JOHNSON CONTROLS 169 FORM 150 62 NM9 709 4 035 21610 104 REV ...
Page 171: ...JOHNSON CONTROLS 171 FORM 150 62 NM9 709 4 035 18150 102 REV D ...
Page 173: ...JOHNSON CONTROLS 173 FORM 150 62 NM9 709 4 ...
Page 175: ...JOHNSON CONTROLS 175 FORM 150 62 NM9 709 4 ...
Page 177: ...JOHNSON CONTROLS 177 FORM 150 62 NM9 709 4 035 21606 104 REV ...