S Y S 1 S W I T C H O F F
S Y S 2 S W I T C H O N
This turns system 1 off
or
S Y S 1 S W I T C H O F F
S Y S 2 S W I T C H O F F
This turns systems 1 & 2 off
Note:
Turning a system off with its system switch allows
a pumpdown to be performed prior to shutdown.
Option 3 – Chilled Liquid Cooling Type:
C H I L L E D L I Q U I D
W A T E R
The chilled liquid is water. The Cooling Setpoint can be
programmed from 40°F to 70°F (4.4°C to 21.1°C)
or
C H I L L E D L I Q U I D
G L Y C O L
The chilled liquid is glycol. The Cooling Setpoint can be
programmed from 10°F to 70°F (-12.2°C to 21.1°C).
“UNIT” KEYS
OPTIONS key
There are many programmable options under the OP-
TIONS key. The OPTIONS key is used to scroll through
the list of options by repeatedly pressing the OPTIONS
key . After the selected option has been displayed, the
UP and DOWN arrow keys are then used to change
that particular option. After the option is changed, the
ENTER/ADV key must be pressed to enter the data into
memory. Table 17 shows the programmable options.
Following are the displays in the order they appear:
Option 1 – Language:
`
D I S P L A Y L A N G U A G E
E N G L I S H
English, Spanish, French, German, and Italian can be
programmed.
Option 2 – System Switches:
(two system units
only)
(Single System Display is similar)
S Y S 1 S W I T C H O N
S Y S 2 S W I T C H O N
This allows both systems to run
or
S Y S 1 S W I T C H O N
S Y S 2 S W I T C H O F F
This turns system 2 off
or
00070VIP
Summary of Contents for YORK YCAL0043E Series
Page 21: ...JOHNSON CONTROLS 21 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 102: ...JOHNSON CONTROLS 102 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 123: ...JOHNSON CONTROLS 123 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 125: ...JOHNSON CONTROLS 125 FORM 150 62 NM9 709 4 ...
Page 127: ...JOHNSON CONTROLS 127 FORM 150 62 NM9 709 4 ...
Page 129: ...JOHNSON CONTROLS 129 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 131: ...JOHNSON CONTROLS 131 FORM 150 62 NM9 709 4 LD08855 035 21627 000 REV B ...
Page 133: ...JOHNSON CONTROLS 133 FORM 150 62 NM9 709 4 035 19213 106 REV C ...
Page 135: ...JOHNSON CONTROLS 135 FORM 150 62 NM9 709 4 ...
Page 137: ...JOHNSON CONTROLS 137 FORM 150 62 NM9 709 4 ...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 62 NM9 709 4 035 21628 000 REV B ...
Page 143: ...JOHNSON CONTROLS 143 FORM 150 62 NM9 709 4 035 19213 105 REV C ...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 62 NM9 709 4 ...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 62 NM9 709 4 ...
Page 149: ...JOHNSON CONTROLS 149 FORM 150 62 NM9 709 4 ...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 62 NM9 709 4 035 21625 000 REV B ...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 62 NM9 709 4 035 19213 104 REV C ...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 62 NM9 709 4 ...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 62 NM9 709 4 ...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 62 NM9 709 4 ...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 62 NM9 709 4 035 21626 000 REV B ...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 62 NM9 709 4 035 19213 103 REV C ...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 62 NM9 709 4 ...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 62 NM9 709 4 LD08833 ...
Page 169: ...JOHNSON CONTROLS 169 FORM 150 62 NM9 709 4 035 21610 104 REV ...
Page 171: ...JOHNSON CONTROLS 171 FORM 150 62 NM9 709 4 035 18150 102 REV D ...
Page 173: ...JOHNSON CONTROLS 173 FORM 150 62 NM9 709 4 ...
Page 175: ...JOHNSON CONTROLS 175 FORM 150 62 NM9 709 4 ...
Page 177: ...JOHNSON CONTROLS 177 FORM 150 62 NM9 709 4 035 21606 104 REV ...